I recently moved in to a new house (15 years old) and the radiators are not heating up properly. The are only hot one side and along the top.
All the rads in the house are original and are piped one side to the top and other side to the bottom opposite ends.
However the house has a...
Thanks for your reply JohnD
So the house is 15 years old but the boiler has been changed a couple of years ago.
It is a combination boiler, is it more likely that the house is plumbed wrong or have the flow and return been mixed up when the new boiler was fitted?
Would it be as simple of...
Hope someone can help.
I have recently moved into a new house, it's 15 years old and has a new boiler, but still the original radiators.
Since I moved in I have found that all but 1 radiator in the house are not heating up properly. They are all warm at the top but cold at the bottom. After...
Thanks for that.
So why is there a netural. Why does the old RTS1 need a neutral but the Digitstat doesnt.
It is the wired digistat i am getting, but out of interest, why would I not have been able to get the wireless one?
Cheers again
Hi
I am looking to change my Drayton RTS1 thermostat, with a Drayton Digistat + 3.
I have a Potterton Puma combi at the moment. There are 3 wires going to the thermostat at the moment
Red (live)
Yellow (switched live)
Blue (netural)
Someone once told me that the Potterton...
Hi
I am looking to change my Drayton RTS1 thermostat, with a Drayton Digistat + 3.
I have a Potterton Puma combi at the moment. There are 3 wires going to the thermostat at the moment
Red (live)
Yellow (switched live)
Blue (netural)
Someone once told me that the Potterton Puma...