@Agile: What's your issue?!? Yes, I put that ad up BEFORE I followed GasGuru's advice and rectified the problem myself, as soon as I did I disabled the advert on ratedpeople. No-one ever contacted me about it anyway and if they did it would be because they thought the price was fair so what's...
GasGuru: I sent an email to as many email addresses I could find at the company with the below:
************************************************************
Helpdesk
I paid £85 + VAT for a diagnosis of my central heating fault. Your engineer, "name ommited", came over and said the...
Well, would you ****ing believe it... GasGuru, you are an absolute LEGEND! The return flow gauze filter was completely clogged, it was like a solid rock!!! I took it out and spent 30 mins scraping it out. Cleaned everything thoroughly and put it all back together, I now have a toasty warm...
Jeez, I am going to be seriously ****ed off with them if this turns out to be the fix! :x
Thank you very much for the advice, I'll give this a go in the morning and report back
Hi all,
Thanks for all the replies, I'll try respond to each of you
@GasGuru - I'm in W3 Acton. The boiler works for hot water but when using CH it heats for a minute or so, makes a loud flowing noise from within the combustion chamber and then switches off. The CH flow pipe gets super...
Hi All
First post after a few months lurking.
I have a Potterton Performa 24 Combi Boiler which needs a new Primary heat exchanger fitting. I had a plumber from a "reputable company" come round yesterday to tell me that I needed a new primary heat exchanger which would cost me £500 for the...