Thanks for your advice but I am competent with gas work I used to do my own before it was regulated I am a semi retired kitchen fitter ,I just wondered what the current requirements are and would be great full for your advice
thanks
Hello, What's the correct set up for a new lpg gas hob ?
the old one has a red regulator and rubber pipe through the wall to the hob.
the pipe is perished so needs replacing, is it best done in copper pipe ?
what size ?
what spec regulator?
dose it need a gas cock ?
thanks
OK, so what we've got is one old white 2.5 cable connected to a MK B32 breaker on the consumer unit this cable runs to a switched double pole
cooker point above the work top the oven is connected via a flexible
white cable coming out of the plaster below the work top
Just measured and the cable will run 8m clipped to joists and above the insulation and down the wall 1.2 through pvc conduit to the cooker point
so am I right in thinking 2.5 t&e will be ok
thanks
Can you tell me what size cable I will need to run a new Lamona 3200
conventional oven. the existing old oven has a 2.5 T&E to the cooker point
but i'm not sure this is suitable the info on the new oven its max output 2400w. So what cable should i use its a clear run of about 8m along the...