  1. A

    shower unit tripping mcb

    thanks for reply.mcb rated at 63A.cable get warm on load side.as you say i will change to 10mm cable
  2. A

    shower unit tripping mcb

    thanks for info plugwash,,i will replace 6mm cable with 10 mm .all other factors which might cause problem are in place.
  3. A

    shower unit tripping mcb

    recently my (triton opal)9kw shower has started tripping the mcb after about 10 mins of use.its run in 6mm about 6meters long and the supply from the mcb does get very warm.suggestions as to why this happening all of a sudden.