    Room Stat problems

    Well I've fitted the motor and that appears to be doing it's job (i.e moving the valve when the room stat is on and off) but it's still not switching the boiler and pump on? Presumably that's done by the valve microswitches? I'm highly suspicous of the operation of one of the two...
  2. A

    Room Stat problems

    Job done, on order :D Screwfix no longer appear to stock them so I got one from Keeptheheaton.com Thanks a lot for your help :D
  3. A

    Room Stat problems

    You were spot on with your diagnosis :D Next questions, do i need to replace the complete valve or can I replace the internal motor? If I need to replace the complete valve is this a do-able diy job for a non-plumber (i.e. me)? Cheers, Andy
  4. A

    Room Stat problems

    Thanks, I'll give that a proper looking into later...
  5. A

    Room Stat problems

    Cheers, thanks for your speedy help :D The schematic shows a junction box/wiring centre, is there a usual place for this to be located? I seem to have loads of junction boxes under my floorboards!
  6. A

    Room Stat problems

    Can anyone please help!!! I have a Honeywell Plan Y system - V4073A Mid Pos Valve, T6060B Room Stat and L641A Boiler Stat with Potterton EP2002 Controller and Glowworm Mk II Boiler. The room stat isnt controlling the boiler, mis position valve or pump? The switched live on the room stat...