Sorry,typo - I meant hot water TANK not pump! I only have the 1 pump.
The model number of the diverter is V4073A1039.
I'll keep the lever on auto. Thanks for that.
I take it the inlet on the bottom of the "T" is hot central heating water from boiler? Where do the 2 outlets wander off to...
Apologies for late get back. Looking at the pictures I have the Diverter valve "B" and I have exactly that Grundfoss pump which as you very wisely say is positioned right by the diverter by the hot water pump.
This morning with central heating OFF I put the switch on Diverter to AUTO and the...
Dave,
I rather naievely think/thought I had a gravity fed system as I have an expansion /top-up tank in the loft above so assume it's gravity fed?
If it's not, does that help you with diagnosis for me!? :)
Brookie
One rad upstairs always got hot but we've lived with that. We've just noticed that the other 3 rads upstairs are doing it as well which is why I want to get it sorted.
The valve in question in airing cupboard has written on it the following;
Honeywell Sundial Y Plan 3 Position Diverter Valve...
When I select heating on, all rads get hot which is nice. But with heating OFF and hot water ON the upstairs rads get hot. Which component/valve is suspect? It's a gravity fed system with a baxi back boiler downstairs and a hot water tank upstairs in airing cupboard.
By the tank is a Honeywell...