    Two isolating transformers in touching distance in bathroom

    Totally agree with what you've said, and I do just that concerning EICRs, I was referring to installation works I carry out but didn't make myself clear. My bad.
  2. C

    Two isolating transformers in touching distance in bathroom

    I know BS7671 are minimum requirements, fitting of fan isolators are normally in the manufacturers literature, or at least in the ones I fit. Think the spirit of my work is to provide easy maintenance, a safe way for local isolation, sadly some diyers may turn off the wrong circuit when trying...
  3. C

    Two isolating transformers in touching distance in bathroom

    Thank you all for the information. I was trying to get my head around the issue and hadn't thought about it before. I carry out many EICRs yearly and like to look primarily at safety. Although the circuit in question was installed in 2000 and under 16th edition regs no RCD was provided. I didn't...
  4. C

    Two isolating transformers in touching distance in bathroom

    I discussed with a lecturer on 18th edition course.... he said that there was a danger and although very unlikely the body would complete the circuit and depending on the resistance of skin (wet or dry) potentially prove fatal. Could it be he was thinking 1 isolating transformer to 2 seperate...
  5. C

    Two isolating transformers in touching distance in bathroom

    Just trying to get my head around this one.. discovered two shaver sockets in a bathroom, 1 in a cabinet, 1 wall mounted. Both sources from same circuit. Scenario is.... plug shaver into one then plug shaver into other. There is a fault on both shavers... so because holding both shavers...