    Nest 3rd Gen Wiring Question

    I decided to connect a light bulb to Terminal 6 and the Neutral terminal and the light only came on when I had the HW schedule set to ON. Your theory about a ghost voltage was correct! Many thanks for that. I'm now good to go. I didn't want to undo the existing system until I was confident...
  2. Colm C.

    Nest 3rd Gen Wiring Question

    It's pumped straight off the boiler to both the CH manifold and the HW cylinder.
  3. Colm C.

    Nest 3rd Gen Wiring Question

    I have a Grant Vortex Condensing Boiler connected to a Systemlink manifold with 4 heating zones (two of which have Nest thermostats connected). I want the new Nest to control the third heating zone and the HW control in the app to switch the boiler ON/OFF. I want to be able to remotely turn on...
  4. Colm C.

    Nest 3rd Gen Wiring Question

    I was just testing my wiring before I installed the heat link and thermostat properly. I was testing terminal 3 and 6 with a phase tester. Terminal 3 will be connected to my heating zone pump and I was intending to connect terminal 6 to the boiler but I was surprised to find that terminal 6...
  5. Colm C.

    Nest 3rd Gen Wiring Question

    I want my new 3rd Gen. Nest to control both a heating zone and the boiler itself so that I can remotely switch it on/off. The heating is working fine (terminal 3 comes live as the heatlink calls for heat) but terminal 6 on the Heat Link is permanently live and does not switch when selecting Hot...