    Baxi 105e Combi-Boiler - DHW problem - No Gas Modulation

    Gas regulation Test 1) sw. off boiler 2) run HW tap until very cold 3) sw. on boiler - observed boiler fire - NO initial regulation (1-2 sec as suggested above) - observed NO Regulation / gas flame change (2-30 seconds) 4) Disconnect / pull black control wire - observed NO...
  2. D

    Baxi 105e Combi-Boiler - DHW problem - No Gas Modulation

    Huh, can't see subject - WIRES ARE BLACK
  3. D

    Baxi 105e Combi-Boiler - DHW problem - No Gas Modulation

    My uncle or cousin will do any gas work i need doing, but as an electrical service eng. Myself there is no harm me doing some diagnostics - especially since the blogs are replete with so called professionals struggling and changing parts willy nilly.
  4. D

    Baxi 105e Combi-Boiler - DHW problem - No Gas Modulation

    Been without HW for over 6 months. Finally diverter valve started leaking so sprung my lazy ass into motion - changed 3 way divertor OK. Central Heating 'appears' to be functioning except I notice that primary heating cct does not reach 80deg - only 70deg - ALL dials set at max (HW and CH)...