Hi @Hugh Jaleak @Madrab
so update.. I went to dog out the trench so I could put the internal pipe in and have hit an old cast iron pipe which must of been the reason the grey pipe was not put in deeper.
if I bring a pipe out here I will have the same problem and it won't be needed deep...
would I only need the water Co permissions if I change anything within the chamber?
or would I still need permissions if I chopped into the stack underground between the bend and chamber
so have found out that this manhole services the property to my left and 2 properties to my right so they all join in.
could I just dig a channel internally and lay the soil pipe at a fall of 1 in 80 and come out of the wall and cap off and then do all the digging around Feb to connect to the...
thank for your help guys! really appreciate it
I have the floor going down in the next 2 weeks but won't have the time to do the outside work.
I'm planning on getting the internal pipping doing and then just cap it off outside until I can get everything dug up etc.
would I just need to...
Hey mate
how does it work connecting down stream would I need come out past the stack under the pavers channel along side the stack and then connect in-between the bend and the inspection chamber
thanks mate yeah I'm doing an extension ATM so anything I do will have to be signed off by BC as well so don't won't to pay silly amounts for something that's not to regs.
I know they do say it's a nightmare with macerators but struggling to see what I could do with this part and I've I can...
Hi mate
there is a toilet the level above
I'm a complete novice here, am I right in assuming you and MadRab are saying there needs to be a minimum of 450mm between the bottom of the bend and the bottom of the new pipe connecting into the stack?
if that's so I don't think it's going to work...
just had a plumber come out and he mentioned about swapping the bed to a 135 degree T and then going into a 90 straight into the wall
said it would be £1200 and that's with me digging the internal trench and knocking through the wall
found some markings on the wall from old owner and it says...
perfect thanks mate
I will get it all exposed and take some photos
I could deffo move the toilet to the opposite end of the cloakroom which would move it down by up to a metre away from the original stack.
Thanks Exedon
so If I was to dig out the 135° bend and replace it could I then connect into the 135° bend, not sure if they make 135° bends with a connector