Spark, sorry mate I did mean ring I'm getting myself confused now lol!
However you raised an interesting point - why the larger cable size for a ring?
Thanks for everyone's correspondence by the way :)
Yes, 32A RCBO radial circuit. Given such a short run and only several socket outlets I can't understand why 4mm is necessary - unless it's something to do with the 17th Edition.
No the cables would be run in the floor void as far as I know (I'm fairly sure this is what will happen).
Or perhaps run in the ceiling void and then dropped to the sockets under capping.
Hi - I specified a 2.5mm2 T&E ring circuit feeding general 13A socket outlets in two small bedroom and an adjoining hall, 32A RCBO at distribution board. I calculated a 5 amp connected load with a 20mm cable run.
The main contractor is making a fuss about the ring being a 4mm2 one - why is...