    GeddyMortgage replied to the thread Bypass valve.
    Generally in the region of 50-75% output id say. when I fire it up it starts low % and gradually creeps up but then as it hits the...
    • IMG_3538.jpg
  • G
    GeddyMortgage replied to the thread Bypass valve.
    I wondered the same as you regarding some sort of failure with an internal ABV @Johntheo5 as in simple terms it does appear that the...
    • IMG_3556.jpeg
  • G
    GeddyMortgage reacted to Johntheo5's post in the thread Bypass valve with Thanks Thanks.
    That boiler has a internal ABV (automatic bypass valve), If it took an hour for the boiler outle to feel like 70C then something...
  • G
    GeddyMortgage replied to the thread Bypass valve.
    Ok so @Johntheo5 @Madrab... I fired it up this evening and monitored it pretty closely myself, I did notice a few things that could help...
  • G
    GeddyMortgage replied to the thread Bypass valve.
    Hey Madrab, I'll try dropping to 70 target and see if that helps things at all but from memory it was the same when I used to run 70...
    • IMG_3519.jpeg
    • IMG_3518.jpeg
  • G
    GeddyMortgage reacted to Johntheo5's post in the thread Bypass valve with Thanks Thanks.
    If the flow temperature is up to its target temp and the boiler is running at 50% output then the heat demand is 50% of the boilers...
  • G
    GeddyMortgage reacted to Madrab's post in the thread Bypass valve with Thanks Thanks.
    No - the boiler modulates down to maintain the output set temps 75deg these days is a bit too hot TBH and If the boiler is overshooting...
  • G
    GeddyMortgage replied to the thread Bypass valve.
    Target temp is 75c. It’s 36kw, and when I add up the kw of the rads at T50, the power requirement for them is around 28kw or so. As...
  • G
    GeddyMortgage replied to the thread Bypass valve.
    It’s been balanced a bunch of times and does seem quite sensitive honestly. It’s 11 type 22 rads and 4 triple column designer types...
  • G
    GeddyMortgage reacted to CountryFan's post in the thread Bypass valve with Thanks Thanks.
    If an external bypass is recommended in the mi’s then one should be fitted, and I doubt the reason for what you’re describing. A bypass...
  • G
    GeddyMortgage replied to the thread Bypass valve.
    thanks @Madrab and @muggles Problem on mine has resurfaced again and wondering if its due to an ABV not being fitted. Im noticing...