    Central Heating Flow Not Getting Past Non-Return Valve

    Ok, I will look at replacing for a single NRV (thinking about what parts I could use so I could easily replace it back to double NRV if needed). The pump impeller looked clean however, I didn't scrutinise the vanes - perhaps I should check again.
  2. G

    Central Heating Flow Not Getting Past Non-Return Valve

    Thanks for the help John, really appreciate the replies! I do not see any other NRVs to compare with unfortunately. Looks like there maybe two options for me here then: - Install a single NRV and fit a spool to make it fit in the 105mm gap from the DCV - Replace the Grundfos Pump head...
  3. G

    Central Heating Flow Not Getting Past Non-Return Valve

    Also, you mention about the 15mm pipe downstream of the DCV - this is not connected (just looks like it on the photo!) It's the cold water inlet and separate.
  4. G

    Central Heating Flow Not Getting Past Non-Return Valve

    Hi John, Cheers, thanks for this. Just to let you know the boiler is Warmflow Kabin-Pak 70 HE (Oil Fired). Is there such thing as a fake Grundfos? To me it looks genuine and yes, it does look newer than the other pump head (DHW pump). However It hasn't been replaced while I have been here (in...
  5. G

    Central Heating Flow Not Getting Past Non-Return Valve

    Hi John, Good question if it really needs to be a double! I'm guessing a single is prone to failing? I've been living at this property for only 2 years and my guess it has always been but I have no idea! Do you know if it is possible to get a 22mm single non return valve with the same length...
  6. G

    Central Heating Flow Not Getting Past Non-Return Valve

    Hi John, Thanks for the reply. It is a combi boiler. The non-return valve is positioned on the heating flow circuit just before it enters the house. I believe it is to prevent back flow due to gravity from the radiators into the central heating pump? Regarding the pump below the central...
  7. G

    Central Heating Flow Not Getting Past Non-Return Valve

    Hi All, So, I am currently having an issue with my central heating provided by my combi-boiler. Every time the central heating is called and the central heating pump turns on, the flow can't get passed the 22mm double non-return valve (labelled by red arrow in attached photo - "Top of Boiler...