    puma 80e ch problem

    Sorry for not getting back to you Chris, but I went out and bought 1 for £70 quid, So I'm a bit gutted after seeing the price you offered it at. O n a happier note, the diagnosis yourself and Kevplumb gave me was spot on and our heating now does what ever we ask it to. cheers, happy xmas Gary.
  2. G

    puma 80e ch problem

    Thanks Chris - but unless you live near in the Camberley Surrey area so we can collect we'll have to buy one locally as the post prob won't get to us in time - although can you let me know how much ??? :)
  3. G

    puma 80e ch problem

    no taps dripping all turned securely off.
  4. G

    puma 80e ch problem

    Hi thanks for the tips and I have checked the following, CH temp sensor is 12.3 kohms cold and 0.7 kohms hot. With the ch on the flow pipe to the diverter heats very quickly to an untouchable temp but the flow on the outlet side of the diverter is very slow to warm up. turning a hot water...
  5. G

    puma 80e ch problem

    thanks for the quick response, the pipes to the rads slightly warm up, some more than others depending on how long and frequent the burner decides to work for. How do I check the diverter valve, cheers.
  6. G

    puma 80e ch problem

    Help, my puma 80e is playing up, DHW is working fine, but CH works only when it feels like it, it seems to light up for about 30 secs then stops and keeps repeating this every 5 mins or so, therefore not really heating the rads. sufficientlly, but will always light up instantly when a hot water...