  1. G

    Soil Stack too close to Velux window

    I'm beginning to agree with your comment about the BCO. Defo only one stack as only one loo when we moved in. Ever asked for a second BCO to give an opinion, I have lost faith in this guy.
  2. G

    Soil Stack too close to Velux window

    It's the only vent :cry: Looks like I'll have to put 2m of stack on for approval then take it off again :wink:
  3. G

    Soil Stack too close to Velux window

    No drawings needed as a simple velux conversion. BCO came round and agreed all positions of windows but didn't notice the stack. The carpenter who did the work will put it right but I want a simple solution as I really don't want the stack moved.
  4. G

    Soil Stack too close to Velux window

    Thanks Eddie. So if I end up with 2m of soil pipe above the gutter line will it need support do you think??
  5. G

    The use and indstallation of a durgo valve

    If the bathroom has an outside wall you could run the stack out through that and up past the guttering.
  6. G

    Soil Stack too close to Velux window

    Hi BCO has come around for final sign off of loft conversion and has just noticed the open soil stack is only about 2.5m from a velux. I know Regs H1 state it must be 3m otherwise you need to go 900mm above window so no arguments with the BCO! He has suggested bringing the pipe inside...