    Wiring worcester 28I to Honeywell cm900 wireless room stat

    i thought i had basically the stat requires the link (which is a perm live also to the receiver)??? unlike a normal prog room sat that does not??? is that correct? :oops:
  2. J

    Wiring worcester 28I to Honeywell cm900 wireless room stat

    I get it now!! Thanks so much for helping me here guys, I really am greatful! I guess I should've bought a wireless stat/receiver which was all of 240v then i'd only have needed 3 wires! Anyway I get it now and will get the wiring done tonight :) It's good to know why you are doing...
  3. J

    Wiring worcester 28I to Honeywell cm900 wireless room stat

    Hi mrgas i do get it (sort of)! in the past i have only wired up normal room stats and a prog room stat, hence my confusion here :oops: Basically, with my boiler, for a normal PROG ROOM STAT: i would need 3 core from the boiler to the prog room stat (or 2 if no neutral was...
  4. J

    Wiring worcester 28I to Honeywell cm900 wireless room stat

    ok thanks for explaining that. i really appreciate you helping me understand how the receiver/stat works. you're gonna flip at me :( but can i ask another question (which'll probably sound daft to you) :oops: : if the receiver is volt free, then why do you need the additional 240v...
  5. J

    hot water takes ages to get hot!

    what's the hot water setting set to on the boiler? it might be the diverter valve diaphragm is failing...
  6. J

    mira sport no water flow

    is water flow at other mains water taps ok? if the electric is ok and no rcd has tripped/fuse blown, etc then it ma be a faulty solenoid valve inside the unit... take the showerhead/hose off and see if water flows then...
  7. J

    mira sport no water flow

    is the water running cold or not at all?? if none at all are any isolation valves to the shower fully open?
  8. J

    Wiring worcester 28I to Honeywell cm900 wireless room stat

    Thanks for explaining mogget, really appreciate it. How comes a wireless receiver for some reason needs another live to it (to make the switch) whereas if i ran a 3 core to a prog room stat i wouldn't need that extra live??... (ie the link)??
  9. J

    Wiring worcester 28I to Honeywell cm900 wireless room stat

    ok thanks for explaining that. so basically, unlike a normal standard programmable room stat (which requires 3 core from the boiler to the prog room stat), the wireless receiver requires an extra live supply to it to the switch, thus the link from the L to the A terminal??
  10. J

    Wiring worcester 28I to Honeywell cm900 wireless room stat

    Thanks for your reply. I will wire as you have stated, but I am not sure why it is this way (it is confusing me)! :cry: I understand how a programmable room thermostat or a programmer and a standard room thermostat can be wired to the worcester 28i junior, but with the wireless room stat's...
  11. J

    Rangers and celtic should be banned.

    Why should the EPL allow Rangers and Celtic into out PL?? They are scottish clubs!!! Why not allow Barca and Real Madrid in or Lyon and Marseille??
  12. J

    BNP win 2 seats

    The reason why the BNP got so many votes (and UKIP to a degree) is because they are the ONLY party that openly ADMITS what many people are thinking/feeling about the immigration problems. It is too much and getting out of hand. It is all well and good for Labour/Conservative members to spout...
  13. J

    Sewage smell from under utility cupboards

    Hiya, How big is the vewnt in your airing cupboard? And what does it look like? Is it an air admittance valve ?
  14. J

    Wiring worcester 28I to Honeywell cm900 wireless room stat

    Hope someone can help :) I have a combi (it is worcester 28i junior) Theres no time clock and room thermostat - so no control over the heating. the water side is fine. Nothing at all here for htg though :( I would like to install a HONEYWELL CM900 wireless room stat / receiver. The...