    spurs

    No, this is impractical since the two FSU's are in completly different areas. The only way of doing it this way would be to wire the FSU's into the ring and run the spurs out from these, since the ring is in the loft and one of the FSU's is switched this is again impractical.
  2. J

    spurs

    Thanks for that Pensdown, I am still confused, the condensed IEE comments are that only one spur may be wired from a socket in a ring why is this different from a JB, also on the blurb on a 30A JB from a well known DIY retailer it says "WARNING" only one socket or spur may be wired into this...
  3. J

    spurs

    If a junction box is installed in the ring circuit(power) and a FSU run from this (5A in this case), can another FSU be wired in to this junction box? or must another box be wired into the ring? This is not a spur from a spur but just two FSU supplies running into one box. thanks John