    Johntheo5 replied to the thread Bypass valve.
    A T50 rad, assuming a room temp of 20C with a flow temp of 75C will require a return temp of 65C to give its rated output, it will...
  • J
    Johntheo5 replied to the thread Bypass valve.
    If the flow temperature is up to its target temp and the boiler is running at 50% output then the heat demand is 50% of the boilers...
  • J
    Johntheo5 replied to the thread Boiler cycling query.
    Yes John, many thanks for all your replies.
  • J
    Johntheo5 replied to the thread Boiler cycling query.
    Run this past me again please. WB say...... . If the burner is lit for a longer duration than the anti-cycle time, then this element...
  • J
    Johntheo5 reacted to Johnytuono's post in the thread Boiler cycling query with Like Like.
    Target flow is 45C, ACT 12 mins and Hysteresis is 7C. No problem at all getting to room temp of 19C although it does take a couple of...
  • J
    Johntheo5 replied to the thread Boiler cycling query.
    Got it now, thanks, I think. Just to be clear, what are your current settings of Target Flow temperature and antcycle ACT time and your...
  • J
    Johntheo5 reacted to Johnytuono's post in the thread Boiler cycling query with Like Like.
    If I set it at 2C from an initial obviously long burn then the 10 minute ACT is fulfilled so the boiler would wait for the 2C drop...
  • J
    Johntheo5 replied to the thread Boiler cycling query.
    A little clearer now, if you set the hysteresis at something daft like 2C, will the boiler just stay OFF for the (10 minute) ACT time or...
  • J
    Johntheo5 reacted to Johnytuono's post in the thread Boiler cycling query with Like Like.
    It starts from scratch again. It seems very different than say, the Vaillant anti cycle mode. If I set 10 mines ACT and the boiler runs...
  • J
    Johntheo5 replied to the thread Boiler cycling query.
    Find a bit difficult to understand this, you set 2.3B to 10 seconds, the boiler may run for only 3 minutes so this leaves minutes of of...
  • J
    Johntheo5 replied to the thread Boiler cycling query.
    I thought the anti cycle time would be as stated below, the amount of time between stops and starts?. The hysteresis function is a nice...
    • 1761811036745.png
  • J
    Johntheo5 reacted to Johnytuono's post in the thread Boiler cycling query with Like Like.
    Very informative, thank you John. It's really trying to find the happy medium. When I was trying the flow at 55c (which still should...
  • J
    Johntheo5 replied to the thread Boiler cycling query.
    Not quite range rating as this only affects the maximum boiler output but will result in a longer run time, also the minimum Off time...
  • J
    Johntheo5 replied to the thread Boiler cycling query.
    A run time of 3600 decs is bordering on constant running, gas fired boilers have a very small HEX volume of ~ 2L or so, so will refire...
  • J
    Johntheo5 replied to the thread Boiler cycling query.
    Boiler efficiency vs comfort? Operational Time per Cycle Base Efficiency Gross Loss Secs % % 3600 85.9 0 180...