    Johntheo5 replied to the thread Bypass valve.
    Didn't "get" your Sat post until about 2 hours ago. OK, first thing is, regarding re pump pressure rise against a closed valve, all...
    • 1770819253056.png
    • 1770819290156.png
    • 1770819378504.png
    • 1770819467032.png
  • J
    Johntheo5 replied to the thread New radiator not getting hot.
    Do these tests with the boiler running, if the rad return is teed back into the main flow, then, when testing with the TRV shut and...
  • J
    Johntheo5 replied to the thread New radiator not getting hot.
    It's possible that it's installed inadvertently as a "one pipe" system, shut off both rad valves then open the vent fully, open the...
  • J
    Yours should look like the attached, (if a Surrey flange). Take a photo if possible, and post.
    • 1770589161357.png
  • J
    If a Surrey flange then the HW is taken from the side and the vent is on the top. If a Warix type then the HW is taken from the Top and...
  • J
    Johntheo5 replied to the thread Bypass valve.
    They shouldn't pass anything if shut, not even 0.2LPM, what's the point otherwise?, you may as well have that gate valve suggested above.
  • J
    Johntheo5 replied to the thread Bypass valve.
    Have you got a actual pressure gauge for doing these tests?, if so, then run the tests by measuring the flowrates at different pressures...
  • J
    Johntheo5 replied to the thread Bypass valve.
    The DU144, according to AI, is Drop Tight.
  • J
    Johntheo5 replied to the thread Bypass valve.
    Using the first pump map of 150mb...... The pump head at 50% speed and even using a 800mb pump = 800x0.5^2, 200mb, a new HEX loss at...
  • J
    Johntheo5 replied to the thread Bypass valve.
    Take all the readings, same as in post #101, please.
  • J
    Johntheo5 reacted to Tonygeek's post in the thread Bypass valve with Like Like.
    Thank you once again John. Presumably the set flow temperature is immaterial for these tests, which I will do as you suggest? I have...
  • J
    Johntheo5 replied to the thread Bypass valve.
    I don't know how (or if) the calculation for residual head is done to give the proper pump speed/output but quite easy to calculate the...
  • J
    When you start the boiler normally then you should see the pressure gauge rise by around o.2/0.3bar, if it does, then possibly a faulty...
  • J
    Johntheo5 reacted to Tonygeek's post in the thread Bypass valve with Like Like.
    I guess the fact that I used a WB accredited installer and that gives me the 12-year warranty, means they will sort any issues with the...
  • J
    Johntheo5 replied to the thread Bypass valve.
    Big improvement with new HEX but again, same as other WB with a new HEX, a 3C dT between Target/Flow temps. Burner cuts out at...