My landlord/agent is the stumbling block for the motorized valve. Hopefully that will be resolved in the next few days..
At the moment I only have a dial thermostat in the hall..
Switching to Npower hopefully in next few weeks.
done the 2 min test.
All radiators TRV's at 4 - heating demand only.
0.096 m3 used for 2 mins or 2.88m3 per hour = 33kw
Hi All, be gentle first post!!
Ok, rented a property for the last year and had gas usage problems from day one.
It is a 4 bedroom detached house (built 2005). Insulated and energy efficient to the max.
I have 14 radiators running from a Potterton performa system boiler 28e situated in...