    Since changing the pump the controller relays stick?!

    Thanks all, after calling Grunfos they sent the suppressor lead that they recommended the next day, I've just fitted it and turned the heating/hotwater on and off a few dozen times and all seems fine. It would usually permanently latch a relay within the first 10 times. So far, no latched...
  2. M

    Since changing the pump the controller relays stick?!

    I phoned Grunfos who instantly said they had heard of this issue before and is resolved by fitting a suppressor lead. The first of these pumps were supplied without leads but due to this sort of issue the lead was issued. They have put a lead in the post, great customer service (fingers crossed...
  3. M

    Since changing the pump the controller relays stick?!

    Its a Grundfos UPS 2 15-50/60, but no strange extra lead?!
  4. M

    Since changing the pump the controller relays stick?!

    This is a slightly strange one. The central heating pump of 25 years old finally died so I replaced it with a grundfos one. All appeared to work fine until I noticed that the old potterton boiler was coming on and the circulation pump was running despite not being set to come on. I...