Recent content by Mista77

  1. M

    part p - consumer unit. tails, rcd help

    Thought I would update all on outcome. The guy came back, put everything right i.e. new box, right way up, new tails, 16mm earth, 10mm bonding, RCD. He stated that the box was untidy but he did his best. He said I have lots of wiring that has been added to by the person who had the house...
  2. M

    part p - consumer unit. tails, rcd help

    It's there but came off when removed cover. Anyone tell which model that is of MK as I am wouldn't mind checking out the specs. i've been on the MK site. Having looked on site here: http://www.mkelectric.co.uk/products/ranges/rangelist.asp?RangeID=1051 Looks like split load cover is...
  3. M

    part p - consumer unit. tails, rcd help

    I see the difference RF lol Will probably take your advice. Kind of want him to explain and do something - change tails and bonding atleast before having to fork out for new job with someone else. RF what is busbar shield please? Thanks
  4. M

    part p - consumer unit. tails, rcd help

    Thanks agian everyone for the fantastic help and support! I am going to get another qualified electrician to look at it and quote what he/she would charge for the correcting job and then try and negotiate the price off the job as he did do some things right! (kitchen sockets I hope?). As I...
  5. M

    part p - consumer unit. tails, rcd help

    One more question. Everyone keeps saying this is a mess. Agreed wiring is a mess aroundthe board, but does that also include the way the wiring has been done inside?
  6. M

    part p - consumer unit. tails, rcd help

    by the way, just thought I would check... has anyone got objections to me printing off this thread and showing it to him? Kind of helps when I know nothing about electrics.
  7. M

    part p - consumer unit. tails, rcd help

    Hi all, Wow! Thanks for all the comments and feedback. I am trying to get someone else in (who knows what they are doing ???) to tell me what's wrong and what they would charge to put it right. I will speak to this guy and give him all the feedback you have given and tell him that either...
  8. M

    part p - consumer unit. tails, rcd help

    Hi fireman22. So I guess the tails are ok? So 10mm would be needed for earthing bonding? I paid £600 to change very old CU, add sockets and lights to kitchen and bonding/earthing. He came and saw job along with 2 others and was the best price. I now realise not always the best thing...
  9. M

    part p - consumer unit. tails, rcd help

    OK. I am getting a little confused, but maybe you guys are checking against each other and I need to be patient. So: 1. Are tails too small. i.e. 10mm? What size should they be: 16mm preferably 25 mm? 2. Old CU was ancient to say the least. Looked like the 1 way wylex CU (which is for...
  10. M

    part p - consumer unit. tails, rcd help

    Ok here are pics of board open, cutout and meter (outside). [ What size do tails/earth look like and what size should they be. He didn't touch any other lectrics that you see around the box, they were there already including weird round junction boxes
  11. M

    part p - consumer unit. tails, rcd help

    by the way that's a 1 penny coin! Don't know if it helps to give you guys a sense of scale. :)
  12. M

    part p - consumer unit. tails, rcd help

    Thanks RF, OK 2 pictures: one of CU and one of tails and bonding. Earth on left is earthing conductor and on right (middle of picture is bonding to gas)
  13. M

    part p - consumer unit. tails, rcd help

    unsure how to use BB tags for images. Will try uploading to other server and then add link
  14. M

    part p - consumer unit. tails, rcd help

    Sure Lectrician. Give me 10 and I will get them for you. Take of unit, tails and bonding. Thanks again
  15. M

    part p - consumer unit. tails, rcd help

    OK. My mistake. Just checked. Tails appear to be 16mm (circumference right?) He appears to have connected 10mm for earthing conductor and 6mm for bonding. Does this souind right? I guess I will have to insist on RCD. Would it be reasonable to pay more for his time isolating the problem or...