Recent content by mozzo

  1. M

    Loud Banging Boiler

    Sorry, misled you a bit. The pressure gauge does decrease when the PRV opens. Anyway, just to let you know, the problem was indeed the pump. Replaced and now works fine. Many thanks
  2. M

    Loud Banging Boiler

    Thanks Kev Is that for sure do you reckon? Is it serviceable or is it a replacement job?
  3. M

    Loud Banging Boiler

    I have a Ravenheat Combi. When the boiler starts up from cold, after about 10 secs, it starts to produce a very loud banging (boiling water). It then shuts off and steam vents from the pressure relief valve (the system pressure remains reasonably stable though at around 1.5 bar). After...
  4. M

    Combi Boiler Pressure Build Up and Loud Banging

    8 yrs old doesn't sound old for a combi boiler. I've seen houses with 15-20 yr old boilers working perfectly. Besides which, being quite a green kind of guy (not to mention carefull, moneywise), it's not really on all that much so I wouldn't expect to have to replace the boiler. Anyway...
  5. M

    Combi Boiler Pressure Build Up and Loud Banging

    Could it be the thermostat?
  6. M

    Combi Boiler Pressure Build Up and Loud Banging

    Thanks again for all replies. When one problem clears, another one appears. I drained the boiler, pumped up the expansion vessel to 0.8bar, closed the drain valve, filled the system to 1.4bar and switched on. The heating worked fine, pressure rose to 1.7bar when the system was up to...
  7. M

    Combi Boiler Pressure Build Up and Loud Banging

    Thanks for all your help guys. Will try it out tomorrow.
  8. M

    Combi Boiler Pressure Build Up and Loud Banging

    Sorry if I sound like a total idiot. How do I drain the boiler?
  9. M

    Combi Boiler Pressure Build Up and Loud Banging

    Thanks for the response Kev. Can you confirm that the expansion vessel can be recharged using an ordinary car foot pump?
  10. M

    Combi Boiler Pressure Build Up and Loud Banging

    I would be very gratefull if someone can give me a clue as to what is wrong with my combi. It's a Ravenheat approx 8 yrs old. It's been a good boiler but recently, when the boiler switches on from very cold i.e. 1st thing in the morning, the pressure on the gauge rises from 1.0bar to 3.0 bar...