    Nelly B replied to the thread Not Getting Hot Enough!.
    Thanks for that desktop. Yes a circulation issue does seem to be the consensus and will investigate with my plumber. The only thing...
  • N
    Nelly B replied to the thread Not Getting Hot Enough!.
    No afraid not. Pump was changed to try to fix the problem. It was quite old and becoming very noisy anyway.
  • N
    Nelly B replied to the thread Not Getting Hot Enough!.
    No I don’t think so ericmark. I have a Salus IT500 smart thermostat and the room never gets anywhere near the set point as I set it...
  • N
    Nelly B replied to the thread Not Getting Hot Enough!.
    Thanks Madrab. Downstairs (7 rads) is 22mm. Upstairs (5 rads) is 15mm as this was done as a chalet bungalow extension. Flow pipe temp is...
  • N
    Nelly B replied to the thread Not Getting Hot Enough!.
    Further to my last post I monitored the boiler during Monday to see if there is any pattern in what it is doing. Boiler control set at...
  • N
    Nelly B replied to the thread Not Getting Hot Enough!.
    Thanks again guys. I believe the radiators are average size although there are 2 doubles. I don't think the pump replacement made any...
  • N
    Nelly B replied to the thread Not Getting Hot Enough!.
    Thanks guys. I have tried putting the heating control to max. This helps in that the radiators now range from 46 to 56 (with a bit...
  • N
    Hi there. I have a Greenstar 24RI boiler and a gravity system with a hot water tank on the ground floor. I have an extended chalet...