    I'd like to avoid a cable to the boiler so a wireless relay it is then. On that, isn't that what the Heatmiser RF Switch is, a wireless relay? Do you know if my idea would work? Install a Heatmiser RF Switch v2 at the boiler as a wireless boiler demand receiver Replace the UH8 with a UH8-RF...
  2. R

    Wireless boiler demand

    Ah nice suggestion, I've just had a look and there's nothing at all connected to the "Heat Enable" part of the control box so I guess I do need a wireless solution
  3. R

    Wireless boiler demand

    Just checked my notes from what the service guy told me and I can confirm it's definitely the factory link that has been left in, putting it into permanent demand mode and that this should be removed and replaced with signals when there is actual demand from the various other system components
  4. R

    Wireless boiler demand

    Yeah thanks, I think that's what they've done. My understanding is that this should be removed and there should only be a call for heat whenever a zone calls for it?
  5. R

    Wireless boiler demand

    Hi, I'm looking for some advice on a control issue with my central heating setup. System components: Vaillant ecoTEC Plus 630 boiler Unvented cylinder with 2-port zone valve controlled by cylinder stat + Drayton Wiser HW schedule UFH with Heatmiser UH8 wiring centre (Yes, the mix of Wiser +...