    Boiler over heating

    Agreed - room stat = no trvs. Just interested to know if all rads on trvs and are closed what is the controlling stat to turn the boiler off before over temperature trips. Can see 3 thermostats in boiler - read inserted in pockets Over temp stat - flow side heat exchanger Water temperature...
  2. R

    Boiler over heating

    No - always tripped on the over temp stat since work started More or less convinced myself that there is an issue with flow Was thinking of running a bypass between the flow and return with a gate valve to adjsut the flow - sound sensible ? How does the boiler cope with a system with TRV's...
  3. R

    Boiler over heating

    No - boiler is for central heating only. Switch is set to fully pumped
  4. R

    Boiler over heating

    Hi, Have just moved into a new commercial unit. Unit was fitted with a Potterton Profile 100E boiler running central heating for 9 rads - all previously working as far as I'm aware. Had the boiler and a few rads relocated last week but now cannot get the boiler to run without the over temp...