  1. S

    Baxi Combi 100 not firing from cold.

    Ok, what's the difference? The replacement looked exactly like the original. When ordering is there a code which identifies the updated version? Cheers John
  2. S

    Baxi Combi 100 not firing from cold.

    I'm not really sure on what is implied by the comment from AGAS above? That aside I have the Gas Safe guy coming tomorrow, it's the same company as the one who serviced the boiler on the 14 of December but possibly a different technician. This problem has developed between the 14th on Dec and...
  3. S

    Baxi Combi 100 not firing from cold.

    Thanks Andrew, perhaps I should use a different Gas Safe Registered Engineer than the one who serviced it last month eh?
  4. S

    Baxi Combi 100 not firing from cold.

    Hi, Situation: I had a problem with my boiler a week ago where is didn't fire up in the morning and was displaying the error 133. I removed the spark ignitor and it was visibly misshapen from heat. I ordered the new part and reshaped the old one in the meantime. It fired up but failed to fire...
  5. S

    Refilling a sealed CH system with the boiler at the highest point

    Reading through the installation manual, I notice: "IMPORTANT: If the boiler is installed at a high point in the system it is strongly recommended that Automatic Air Vent Kit 720004701 is fitted. Ensure that this vent is open." A quick search of this reveals something which looks a lot like...
  6. S

    Refilling a sealed CH system with the boiler at the highest point

    Hi, thanks for the responses. The boiler is a Baxi Duo-Tec combi 28 (the one with the dials, not the central LCD screen). On the top of the pump is a brass device referred to in the manual as the Automatic Air Vent. Interestingly, there is another one which is fitted above the boiler protruding...
  7. S

    Refilling a sealed CH system with the boiler at the highest point

    The situation: Having recently found a leak in a micro-bore pipe, thanks to a plasterboard screw going right through it. I decided to fully drain the system during the repair and fill with a system cleaner to run for a few days and then drain and refill with inhibitor. The initial problem: Upon...