I totally disconnected the 3 port valve from the system. I then turned the system on (the boiler fires and the pump starts working THE FUSE DIDN’T BLOW). I also removed the actuator on the 3 port; the head is clean with no sign of leakage.
Thanks again for your fast responses.
Regards...
Thanks for your quick replys guys.
I have a baxi solo boiler. Sorry i didnt mention in earlier post.
Regards,
Spottyfrog.
PS. My pump is not wet and no evidence of leaks in past.
Hi guys, before I start explaining my problem I would like to say hello to everyone as I’m new to this forum.