cheers paul, start ups had crossed my mind forgot to take that into consideration on calcs but must have been going in the back of my mind when i was testing the system, because i let the system cool ensuring all parts ran at once. I have since found out that it has only happend twice (bleeping...
re total load
zone valves 6w x 4
boilers 110w x 2
under floor heating heads 4w x 5
programmer 4w
room stats x3
cyl stat x2
total less than 720w (3a fuse)
tried a 5 and it blew that aswell then just started working again just wondering if a zone valve or manifold head was sticking a...
i have been asked to look into a boiler system that blows the 3a main fuse in the spur occasionally ie 4months apart then three fuses in a row
the system contains 4 zone valves controlling 2 hot water cylinders with individual cyl stats central heating via room stat and under floor heating...
i have been asked to look into a boiler system that blows the 3a main fuse in the spur occasionally ie 4months apart then three fuses in a row
the system contains 4 zone valves controlling 2 hot water cylinders with individual cyl stats central heating via room stat and under floor heating...