Recent content by Stubee

  1. S

    Boiler choice- Worcester or Ferroli

    Hello, I'm looking to get a new combi boiler installed soon, the choices from our favoured plumber are a Worcester Greenstar 30CDi or a Ferroli Opitimax 31C. What do people think about these boilers? The Ferroli comes with the 5 year gurantee (which hopefully shouldn't be needed?) which is...
  2. S

    Ideal Response 80!! Intermittent ignition

    Well this afternoon it switched on fine when HW demanded but wouldn't ignite when CH selected on. I guess I'll see what the gasman says if I can get one round, just I don't want to flog a dead horse.
  3. S

    Ideal Response 80!! Intermittent ignition

    Hello, my boiler has been tempremental of late. When the CH is switched on from cold it doesn't light sometimes taking several attempts. One way to get it to light would be to turn the hot tap on which would light the boiler then select CH on. After that it is fine until the next 'cold start'...
  4. S

    Ideal response 80...

    Thanks Gaz, found it under a cover on the top, water drained and air pressure topped upto 0.5 bar and then water refilled to 1 bar. So far so good... :o Pressure has risen a bit an PRV seems ok. Might have earnt mi sen a pint :D
  5. S

    Ideal response 80...

    I see the red expansion vessel, with a drain tap underneath but I can't see a schrader valve or whater it is to admit the air. Where does it reside on these? Thanks again.
  6. S

    Ideal response 80...

    Hello, seems these boilers feature a lot here! Anyway my problem having read through these pages appears to be similar to no air in the expansion vessel (pressure drops when off, rises upto 3 whn swithced on and the safety valve passing water). However I'm a little unsure if it just a case of...