it was a relief this morning to get up and find - 1 bar in the system.
need to get it dosed up tonight - some fernox cleaner to go in for now.
can any one suggest a good all in one inhibitor/antifreeze for the system - its an external combi.
we get extended power cuts during winter...
Sorted.
Suspected the pressure gauge was shot , i was right , stuck my pump on the expansion vessel
Pressured the system back up.
1 bar in the vessel . Put pressure in the system , up to 2 bar . Gauge reads zero. Put gauge to 1 bar and it reads 2 , so the boiler trips the prv when it...
Got a grant vortex 26e
Couple years old
had a new expansion vessel and prv fitted not so long ago - was dropping pressure over a couple of weeks before this.
Now its started gurgling the radiators upstairs at 4am when the heatings due to come on and dumping pressure somewhere. Yet it...
first post here , probably first of many im sure.
Ive got a 4 foot ventilated airgap under my floor.
the floor its self is a sectional steel reinforced concrete sitting on top of brick foundations.
The dirt on the floor of the crawl space is damp to touch after heavy rain due to...