Mmm I never considered that, I assumed (wrongly) that you can't spur directly off a mcb on a ring circuit.
I assume I just connect to the same CU neutral and earth terminal as the ring to make it obvious for any future inspection.
The conservatory sockets are not power hungry.. small...
Many thanks for all of the replies, having read over this and the IET forums I see that the notifiable questions always spark debate (pun intended).
In response to some of the posted questions:
1. The external garage CU is fed from the house via 6mm SWA cable, so that's from a 40A in the house...
Hi, tried to find a similar thread but nothing was quite as specific.
I've got a CU in a garage with a 20A radial in 2.5mm T&E feeding 4 double sockets.
I plan to put the put the washing machine in there (already has a dryer and a fridge freezer) to make some kitchen space.
My slight concern...