Simon and Boilerman, thank you for your help. I have found a small inline filter/mesh just before the cold inlet isolating valve. It was packed off with crud and hence no flow. Its all working again now . There are lumps of scale coming out of the taps ocasionally, i'm thinking this might be...
Must be a blockage then. The cold supply comes straight from a jet pump with 25lit storage at 3-5 bar. I'll break open a connection at the blend valve and work back till i find water.
Thanks
Thanks simon, i'll look at the blending valve tomorrow. Is it cleanable or am i better to replace? Is the hot water 'driven' by the pump or is it the mains cold pressure that pushes the hot water?
Thanks
hi, i have a grant combi 90 boiler with a fault. The central heating works ok but there is no flow from the hot water taps. There is no water flow at all at any hot tap. If i push a matchstick into the microswitch on the front of the diverter valve then the boiler fires up. The pin on the...