Recent content by zignafio

  1. Z

    3 port valve problem

    [email protected] be more than happy to help
  2. Z

    3 port valve problem

    Thanks seco, If you ever have any asbestos queries drop me a line, info, help, advice, im here for yah.
  3. Z

    3 port valve problem

    removing the layers as we speak. cheers bud
  4. Z

    3 port valve problem

    your a legend, cant thank you enough. gonna leave it on all night and sweat my balls off. Cheers fella. Mrs says thanks too.
  5. Z

    3 port valve problem

    Seco, trust me it is when you aint had none for three days. think i get what you mean with Cyl Stat. no problem with that. Valve does hold in position but boiler doesnt fire up, if i hold it up above its resting position like a cpl of mm boiler fires up, the second i let go boiler stops working...
  6. Z

    3 port valve problem

    Cheers seco, im assuming i would need some sort of electrical test gear to do that and dont have it so no joy there, like i said the strange thing is if i push the manual thingy a little more, and i mean like 2 or 3mm more than the actual resting position it all works fine, i just dont fancy...
  7. Z

    3 port valve problem

    Thanks Seco, if only i knew what that meant. Would installing a new Actuator solve the problem or am i wasting my time. Thanks again for fast response Zig
  8. Z

    3 port valve problem

    Hi there, I have had a problem with my central heating over the past couple of days. Problem being I had hot water but no heating. After a few hours scouring google etc. i come to the conclusion that my problem was with the 3 port valve. the make is a salus 322 and up until 10 minutes ago i...