Vailant ecoTEC 630 Wiring Question

Joined
15 Jan 2008
Messages
191
Reaction score
13
Country
United Kingdom
Hello. What is the purpose of wiring the heating / hot water controls across terminals 3 & 4 of this boiler? What additional protection / safety is gained by taking the supply to the controls from terminal 3 as opposed to supplying the controls direct from the spur supplying the boiler and then just sending the switch live to terminal 4?

I hope this query is clear?!

Thanks
 
Sponsored Links
On older Vaillants the OH stat could be bypassed by wiring this way.

To answer your question, the mains I/O switch on the facia does not isolate the boiler if you take an external phase conductor into 4. This obviously has safety implications for the unaware.
 