    Indirect cylinders.

    True. Never thought of that. Heating and fire are staying off until next cylinder goes in. Glad it's not the middle of winter. The nearest plumber is 20 miles away so have to wait in line. Thanks for comments.
  2. P

    Indirect cylinders.

    Would it still boil even though the central heating is pumped from the same stove?
  3. P

    Indirect cylinders.

    Can anyone help? Replaced hot water indirect cylinder which was leaking with the same size cylinder. Radiators are fine but can only get hot water if immersion is on. Spent some time looking for an airlock and checking for dirt in system but no luck. Didn't realise we had to specify that we...
  4. P

    Expansion tank?

    Thanks for reply. It's not really his fault as it was meant to be a straight swap of a leaking cylinder for a new one. The boiler is a multifuel stove and it is vented. It was too late and too warm last weekend to fire it up. It filled and there were no leaks and we checked the immersion heater...
  5. P

    Expansion tank?

    Cylinder is replaced, same size as old one, indirect and vented. F&E tank installed, new immersion heater as well and all radiators are bled and heating. Can't get hot water though unless the immersion is on. Spent all weekend hunting an airlock and checking for a blockage but no joy. We find...
  6. P

    Expansion tank?

    There is an automatic vent as part of the design of the Spartan vessel. It's the little grey bit at the front about the size of a Heinz baby food can. I assume because both the heating and domestic water goes through this Spartan thing that the one vent does both. The thing is it's worked fine...
  7. P

    Expansion tank?

    It is def the hot water from the cylinder via the top of the Spartan vessel that goes to the bathroom and kitchen DHW. Plumber is coming to replace indirect cylinder later this week and will see if a F & E tank is able to go in.
  8. P

    Expansion tank?

    Not sure about that. I can only see 3 pipes going to loft. 2 cold water mains for my house and the upstairs house and the return cold water pipe for my domestic supply. Doesn't appear to be a vent. If we put a F&E tank above the cylinder it will be a metre from top of radiator to water level in...
  9. P

    Expansion tank?

    Yes it does. Comes back down into a walk in cupboard to the right and goes to bathroom and kitchen sink.
  10. P

    Expansion tank?

    Turns out the Hydro Spartan is leaking too. Take it there is nothing similar to the Spartan on the market, Is it feasible to put the F&E tank above the hot water cylinder. Height to ceiling is 1.3m. 1.75m from radiator to ceiling. Can't get a picture of the boiler connection as it is behind...
  11. P

    Expansion tank?

    The woodwork is due for the chop tomorrow. Need to get the old tank out. Can post a better pic then.
  12. P

    Expansion tank?

    The hot water feed to the bathroom taps is the right hand side pipe. Can get a digital camera tomorrow if the pics are not clear.
  13. P

    Expansion tank?

    I am. Sorry. The pipe at the back is the hot water pipe which goes to the bathroom and then back into the kitchen sink.
  14. P

    Expansion tank?

    There is one more connection coming out the bottom of the Spartan cylinder. Can't get in to take a clear picture. The air vent is the smaller grey colour cylinder on the bottom left. My apologies but this is my first time on this site and I haven't worked out why my pics turn sideways and how to...
  15. P

    Expansion tank?

    We burn smokeless fuel and logs. Think it was installed mid 90's and by a plumber and a builder. It's a Hamlet inset stove with a back boiler which replaced an open fire.
  16. P

    Expansion tank?

    There is no F&E tank. After consulting neighbours the council put central heating in these house in c1990 and they appear to have used these Spartan vessels rather than putting the F&E tank in the upstairs house attic. Don't know what my rights are regarding access to install a tank in someone...
  17. P

    Expansion tank?

    Would it be feasible to replace this with 2 expansion vessels on each side of the system?
  18. P

    Expansion tank?

    A multi fuel stove. There are 7 radiators and hot water to bathroom and kitchen. No bath as there is an electric shower.
  19. P

    Expansion tank?

    Thank you for reply (and help with pictures). We have no access to loft space because we're a ground floor flat, ex council house. Realise now there is no feeder tank. What are my options ie is there an equivalent to this Spartan cylinder or should I be looking at a combination indirect cylinder.
  20. P

    Expansion tank?

    Sorry, pics have turned sideways for some reason. Hope they are clear enough.