    Downstairs heating only working when upstairs is on

    WARNING. Do not attempt to measure resistance on live conductors
  2. T

    Downstairs heating only working when upstairs is on

    230/240 volts between the orange wires terminal and earth terminal when downstairs valve only is on calling for heat.
  3. T

    Downstairs heating only working when upstairs is on

    Yes ,you would need to do some voltage testing to establish if the orange wire at the wiring centre reads 230/240 volts . Are you competent to work safely on live circuitry ?
  4. T

    Downstairs heating only working when upstairs is on

    The motorised valve sends the voltage to the boiler to fire it up. The motorised valve gets its voltage from the thermostat.
  5. T

    Downstairs heating only working when upstairs is on

    If the upstairs is switched on ,fires up the boiler,and downstairs switched off ( no call for heat from downstairs stat),do the downstairs rads still heat up ? If so ,the valve body of the downstairs valve must be physically stuck open.
  6. T

    Heating downstairs only works if upstairs is called.

    You should really start your own thread to get more response.
  7. T

    Hanging column radiator

    I tend to fit the top brackets ,hang the rad ,then present the bottom brackets in situ. Mark their positions,take rad off ,and then fix the bottom brackets.
  8. T

    Boiler fix or replace advice

    What was the engineers diagnosis,and what parts were suggested that needed replacing ?
  9. T

    Dishwasher water inflow pipe wont fit

    Yes it could . (y) (y)
  10. T

    Dishwasher water inflow pipe wont fit

    Not quite. The thread of the isolation valve in your pic ( what the tap tail screws onto) is 1/2 inch BSP. The washing machine / dishwasher hose thread is 3/4 inch BSP. The Tee in your link is not correct. An equal Tee can be used but it would have to be fitted onto the copper,after the...
  11. T

    Dishwasher water inflow pipe wont fit

    You should introduce a Tee into the copper supply pipe and extend from it to an appliance isolation valve .
  12. T

    Cold radiator. Please please help

    Is the problem radiator a vertical / designer type ,or a standard panel radiator ? Given the fact that the problem rad heats fully when all others are closed off ,then there isn't anything wrong with it ,or it's valves. Close every other rads lockshield valve fully ,open the problem rads...
  13. T

    Cold radiator. Please please help

    Who balanced the system ,and how ?
  14. T

    Self inflicted leaking towel radiator

    Is the leak only where the brass part screws into the chrome valve body ? If so ,is the brass part fully tightened up ? It should be fairly easy to make that joint watertight, if you are relatively confident on working on the plumbing.
  15. T

    Flush siphon unit / filling valve too big for existing cistern?

    Yes it is. That doesn't look like a new pan and cistern. What exactly were you doing ,just fitting new float valve and siphon ?
  16. T

    Flush siphon unit / filling valve too big for existing cistern?

    Why not take the cistern to a decent plumbers merchant who can supply one that fits. A flush valve is usually operated by a flush button ,but you can get lever operated ones. A siphon is what you have. Is the WC close coupled ,or is there a flush pipe ?
  17. T

    Replaced loo fill valve but still dripping.

    Can't say I have ever used prestex tap con washers,but they look the same as any others.
  18. T

    Replaced loo fill valve but still dripping.

    And you need to remove all traces of the old washer so the fitting is nice and clean before fitting the new washer.
  19. T

    Replaced loo fill valve but still dripping.

    That's a 1/2 inch, fibre ,tap connector washer.