    UFH condensing oil boiler short cycling

    I think with all the very helpful advice for which I am extremly grateful, I have exhausted most of all the various permutations regarding boiler temperature and both pumps speed settings. Really there has been little difference but - we tried. Thank you Johntheo5 re all your comments and advice...
  2. M

    UFH condensing oil boiler short cycling

    With both pumps set at 2 - over a 20 minute period after boiler had been on for 3 hours - it fired up for 6 minutes out of those 20 and was off for 14 minutes. There was 6 on and 6 off cycles and pump at boiler showed 40 - 44 watts! If run time is 30% ie 20 minutes per hour does that compare to...
  3. M

    UFH condensing oil boiler short cycling

    Whoops - previously I said floor area for ufh was 50m2! It's actually 147m2 or 1592ft2
  4. M

    UFH condensing oil boiler short cycling

    The manifold temps for the most recent cycles were 48c in and 40c return. Ive since reduced boiler temp to 60c and l'll drop the grundfos pump to speed 2. Will report back! Do you think dropping a nozzle size from 1.15 to 1.0 might help in reducing hopefully boiler firing run times. I wonder is...
  5. M

    UFH condensing oil boiler short cycling

    Ok, with Wilo set at pump speed II the watts range from 39w when not firing to 44w when firing. Firing time on average over 3 cycles etc was 2'43'' off and 1'01'' minutes firing. Thermostat was 65c I think. What do you reckon next- should we reduce pump speed to I and monitor? The ufh pump is...
  6. M

    UFH condensing oil boiler short cycling

    I have kept a spreadsheet over the past 20 years noting oil purchases and how long until next one! Each year over the 20 years ranges from 4500L to 5500L - your 1400 annual litres would just about last me 3 winter months. I'm on first name terms with oil tanker driver - his quickest delivery...
  7. M

    UFH condensing oil boiler short cycling

    The HW was the only circuit on during summer months and used about 5L of oil a day. It comes on maybe 1 min in 10 but will monitor as well. The upstairs radiators come on in morning when I'm still in bed and come on at night when I'm in bed! They are on for 30 mins each time and heat up we'll...
  8. M

    UFH condensing oil boiler short cycling

    Thanks so much for sharing all your knowledge - I've put Wilo pump at speed 2 and will monitor. I'll likely not get a chance for a few days as working in my retirement job for a large UK retailer selling Percy Pigs!! Strangely the on and off times when set at 6.0 seemed to vary from 1 on/3 off...
  9. M

    UFH condensing oil boiler short cycling

    Oh, the dial on the Wilo pump is on the left at image of middle sized house
  10. M

    UFH condensing oil boiler short cycling

    I checked the burner in my garage and it efforts says RDB 2.2BX V26-46! Turned Wilo pump dial on the return to the boiler anticlockwise until it showed 6.0. The wattage ranges from 49w to 61w. The boiler has been firing for nearly 2 hours on UFH only and is now firing on for 2-3 minutes (5min...
  11. M

    UFH condensing oil boiler short cycling

    Further apologies - Commissioning Passport by Engineer shows burner to be RDB 2.2BX v26-46!! Night night now!
  12. M

    UFH condensing oil boiler short cycling

    Sorry - the Grant boilerhouse manuals (online and paper copy) show different factory fitting nozzles so mine could be 1.1 or 1.25! Also, the online manual (UK rev July 22) does say it's a 26-46 though the boiler top plate says 36-46! The manual that accompanied the boiler is IRL June 23 shows...
  13. M

    UFH condensing oil boiler short cycling

    I'll let you know how the pump fiddling works! It does appear to be, according to metal plate on top of my boiler, that it is a Grant Boilerhouse 36 - 46 factory fitted with a 1.25 nozzle giving out 41kw. A 1.00 nozzle will reduce this to 36kw. The Riello burner on the boiler is RDB 2.2BX...
  14. M

    UFH condensing oil boiler short cycling

    I'll fiddle with pump in the morning and I'll check with Grant again re lowest nozzle size but I'm sure it says on top of boiler 36-46 but again - will have a look in the morning!
  15. M

    UFH condensing oil boiler short cycling

    Wilo was pointing to right but to Number 3 setting!!
  16. M

    UFH condensing oil boiler short cycling

    There are only 2 pumps! One is on the heating return and is a Wilo - Yonas Pico. It's currently set for large house consuming 75w? but seems to modulate down to 58w! The supply for the UFH comes off a T pipe from the supply to the upstairs radiators and is pumped round UFH by a Grundfos 25-80...
  17. M

    UFH condensing oil boiler short cycling

    Shall do but will be later - grateful for your helpful comments
  18. M

    UFH condensing oil boiler short cycling

    Additionally the water circulating in the pipes around the boiler is noisy! You can certainly hear it!