Search results

  1. T

    Maintenance free junction box under floorboard

    Thanks. is the 'Hylec Debox 4 pole junction box' classed as not maintenance free ie can only be used inside an access panel (e.g. 1 gang plate and backbox)?
  2. T

    Maintenance free junction box under floorboard

    Are the Ashley J804 suitable for 1.5mm electric cables? I also have about 10 pre existing (ie signed off by electrician) of 'Essentials 30A 3-Terminal Heavy Duty Junction Box Black'...
  3. T

    Maintenance free junction box under floorboard

    I'm 'making good' an existing electrical installation in a terrace alongside lowering the ground floor ceiling. As such with the electrics under the upstairs floorboards I am doing: -Clipping the electric cables to the joists at 50% depth as the electric cables were not clipped at all...
  4. T

    Accidental nick to socket cable

    Image (2) is the 2.5mm2 cable nick turns out it was only through the outer sheath and did not go through the inner sheath no sign of exposed copper. Pic (filename ending ..535) I decided to wrap electrical tape around the cable, then put waterproof tape over that and then use cable ties to make...
  5. T

    Accidental nick to socket cable

    That's what I'm doing 1st thing tomorrow, and if there's no exposed copper I'll wrap tape around it and leave alone
  6. T

    Accidental nick to socket cable

    Probably the neutral copper as I can see (bear in mind the cut is literally 4mm across and less than 1 mm deep) a bit of blue. It's a tiny cut literally a glancing cut from a multi cutter not a full 'go through'
  7. T

    Accidental nick to socket cable

    Brilliant thanks. I will turn the B32 RCBO off, test the wire using a voltage tester then see if the wire is actually nicked (exposed copper) if the sheath is cut but the live/earth/neutral wires are not then I'll tape over it. If the live/earth/neutral is cut I will then relocate the socket...
  8. T

    Accidental nick to socket cable

    The copper is very likely exposed. Can I relocate the 2 gang socket down so it's 28cm from ground? Then no additional joints needed
  9. T

    Accidental nick to socket cable

    Can I move the socket down 8cm so it's 28cm from ground (is this ok and in accordance with UK regs)? If I can then I don't need to create another joint
  10. T

    Accidental nick to socket cable

    I don't know if the earth wire was nicked aswell Happy to move the socket down provided the socket can be 28cm from ground? From what I've read all electrical joints need to be accessible and this is best practice
  11. T

    Accidental nick to socket cable

    I have read that electricians don't like maintenance free joints as they can't see them so my plan of using 3 x 32A inline spring connectors inside a backbox covered by a 1 gang plate (which is accessible) seems to tick the boxes. This plan allows the joint to be accessed whilst using Wago...
  12. T

    Accidental nick to socket cable

    I would use an in line spring clamp connector (https://www.toolstation.com/wago-221-2-way-inline-lever-connectors/pAC293) with no heatshrink tubing (as it's not needed I just remove 1cm off sheath off line/earth/neutral. The 3 connectors would be inside a 1 gang accessible backbox covered by a 1...
  13. T

    Accidental nick to socket cable

    Is about 1cm bare copper on each end of the cable enough to fit into these wago in line connectors?
  14. T

    Accidental nick to socket cable

    ignore
  15. T

    Accidental nick to socket cable

    My mistake the 45cm socket height is recent guidance not a requirement
  16. T

    Accidental nick to socket cable

    I have no experience with heat shrink tubing and the 'WAGO 221 2-Way Inline Lever Connectors 32A 0.2-4mm²' (https://www.toolstation.com/wago-221-2-way-inline-lever-connectors/pAC293) is lever compressed (no soldering/special tools/heat shrink) needed so I (as a DIY'er) can do this myself...
  17. T

    Accidental nick to socket cable

    No I'd rather just cut the nicked cable 8cm (where the nick is) then join live/neutral/earth together with the 2-way line wago connectors (wago connectors would be inside an accessible 1 gang backbox with front plate). Not going to replace the short piece to socket. Sounds ok?
  18. T

    Accidental nick to socket cable

    There is not enough flex in the cable for 180 degree turns. So I would use this wago instead x 3 (one live one neutral one earth): WAGO 221 2-Way Inline Lever Connectors 32A 0.2-4mm²: https://www.toolstation.com/wago-221-2-way-inline-lever-connectors/pAC293 is this ok?
  19. T

    Accidental nick to socket cable

    So, out of the options below: 1. Connector Strips 30A, https://www.toolstation.com/connector-strips/pAE651 2. In Line Spring Lever Connectors 3 Pole 32A, https://www.toolstation.com/in-line-spring-lever-connectors/p78346 which one would you pick and why?
  20. T

    Accidental nick to socket cable

    I've read that electricians don't like hidden maintenance free joints behind plaster and that one should use visible plates for access. Also, as the ring main is 32A I would use a Spring Lever Connectors 3 Terminal 32A (https://www.toolstation.com/in-line-spring-lever-connectors/p78346) which...
Back
Top