  1. R

    underfloor heating only works in some rooms

    also, what temp should the supply water be at the manifold? cheetrs
  2. R

    underfloor heating only works in some rooms

    thats great thanks. not to question you or suggest it makes much of a differnce , but have read the diff shout be about 12?
  3. R

    underfloor heating only works in some rooms

    could the blending valve be faulty? i have read people taking them off and cleaning etc. how is this done?
  4. R

    underfloor heating only works in some rooms

    the blending valve is set to 45/50 as previously mentioned. there is a thermometer in the supply to the manifold pipe as well as the return pipe on the manifold. the supply thermometer reads 70 and the return can be reading 40 degrees sometimes
  5. R

    underfloor heating only works in some rooms

    i think the supplly is like 70 and the return coming back at 45/50
  6. R

    underfloor heating only works in some rooms

    ah well i will try to tighten up the temp differecnes then
  7. R

    underfloor heating only works in some rooms

    Hi all, have a wet underfloor heating system. the issue i have is that some rooms/loops work fine and others the floor stays stone cold. new pump was fitted and the supply is hot so no issues there. blending valve set to 45/50 and the flows all read about 2ltrs. the returns come back luke...
  8. R

    purging underfloor heating

    also, what pressure should the system be on?
  9. R

    purging underfloor heating

    my manifold is below all the floors...
  10. R

    purging underfloor heating

    well I can close one end of the loop as it were , but wont it continue draining into the manifold etc?
  11. R

    purging underfloor heating

    HI ALL. last ditch attempt to get my UFH working in some rooms,some are fine. I want to purge the system of air which im fine to attempt. my problem is that I can close both ends of the individual loops . I have the balancing valves at one end of each loop where I can screw them down to stop the...
  12. R

    Underfloor heating problem

    No carpets its wood floor
  13. R

    Underfloor heating problem

    cheers, i'll go and hire a power flusher etc
  14. R

    Underfloor heating problem

    Yes ,I've had it running for most of a day and still nothing.
  15. R

    Underfloor heating problem

    sorry to double post, but if there is some crud blocking it, and cleaning fluid helps budge it, could the dirt/ whatever block somewhere else?
  16. R

    Underfloor heating problem

    so I just introduce the cleaner thru the manifold filling point? or how do I put it through? I guess the same with the inhibitor?
  17. R

    Underfloor heating problem

    what product do u think I could try to introduce my self? is it ok to leave it in the system for that long etc?
  18. R

    Underfloor heating problem

    good point.. perhaps I'll just bite the bullet and get someone ELSE in! thanks for all your help and advice buddy
  19. R

    Underfloor heating problem

    when I feel the floor by hand it feel stone cold. is the power flush something I can do my self , or do I need some sort of pump etc? when I purged the loop the water coming out was clear...