  1. Jajodu

    Downstairs heating turning itself on, upstairs fine?

    Suspect valve no 8 in your schematic, sticking on and firing up the boiler.
  2. Jajodu

    Can you put a bleed screw on the other end of a radiator ?

    Can't see why not. Best of luck unscrewing that end though.
  3. Jajodu

    Vaillant boiler high pitch sound /whistle

    Sounds like the fan, does it only occur when the burner is going? Does it stop when the burner exstinguishes, if not it may be the pump.
  4. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    Excellent. Glad you're sorted. Thought it was strange with no fault codes.
  5. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    That was quick. Did you have a spare?
  6. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    Do you get the pump symbol on the display? The nomal sequence is demand, pump symbol, then gas flame symbol. So the boiler looks for flow, if ok it then open the gas valve by activating the fan, flame supervision to detect ignition, then after a minute turns gas up to full rate. How long before...
  7. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    Can you hear the pump starting?
  8. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    Look in your instructions and look for d codes and how to read them. I.e. fails to light or pump errors.
  9. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    I'd expect it to show a fault code. If it doesn't detect a flow, pump running. It won't fire up but it should show a fault.
  10. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    Does it get past s97?.
  11. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    What's the display showing with the I button selected while doing this?
  12. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    So if you disconnect these wires from the hive and jumper the two pins on the 24v rt connections the boiler doesnt fire up?
  13. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    Which connection are your external controls connected to?
  14. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    You should have 240v not 24 on those terminals. Don't like the flash on the pcb though
  15. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    Post a picture of the wiring into the boiler please. If you bridge 3&4 does the boiler fire up, if not measure the voltage on both with a multimeter, one probe on the negative in, the the other on either 3 or 4, what doe you get? You need to see 240 V on at least one of them
  16. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    Then it's external, S30 is no request for heat.
  17. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    So if you observe the led panel using the i button what sequence do you get please. Do you have the install instructions? It lists all the S codes to explain their meaning.
  18. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    In that case it should show an error code if it fails to run.
  19. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    Have you reinstalled the pump. It won't run without it and will shutdown as soon as it detects a no flow situation.
  20. Jajodu

    Dead boiler Vailant Ecotec Pro 28

    You can wire the pump directly into a mains supply if you're confident with wiring to see if it works. Use a 5A fuse. You'll soon see if it blows the fuse. So not connected to the boiler electrically at all, just into a mains plug.