    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Yes that is exactly what it is with your descriptions there. It looks like a combined vent and cold feed.
  2. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Thanks for the advice. When you say slackening back you mean to drain down the system below the level of the pipework? Also when you say re manual iso level valve and the automatic vent valve so it can then be easily isolated if it start dribbling what do you exactly mean by it start dribbling?
  3. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Yes I tested that with a magnet (see a few posts above with pictures) and the magnet did attach. I still do not follow why only HW flow has issues though?
  4. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    The test here you mean expansion of water discharged through vent pipe into the F&E tank?
  5. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Open vented system AFAIK. I will have to do the HW&CH to HW test and report back. I think the setting before I boxed it up was that it was just CH on as the last test of manual spindle changes. The boiler SP (if you mean the temperature gauge - attached) on the boiler is currently set to HIGH...
  6. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Looks like something is blocking the flow when in HW only and actually when in the loft doing the manual spindle switch to HW only (programmer on HW only too) I observed the gurgling and pipe wobble until I bled the vent by the coil. It was 14W that went up to 16W after bleeding. Could the HW...
  7. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Ok so I boxed it all up and redone the tests: 1) HW only - boiler runs for 30sec or so (probably from previous mid position) and stops even though cylinder stat cranked up to 70C before the test, pump shows 18W 2) HW & CH - boiler fires up and runs indefinitely when room stat cranked up to 27C...
  8. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    I did put programmer to CH only, change the spindle of the valve manually to CH only and room stat calling for heat fires the boilerup but stops at some point and goes to stand by. The pump shows 18W. What is bizarre is that when I switched the spindle manually back to HW only (everything else...
  9. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Thanks for your help @Johntheo5. Ok so I did this test: "...maybe try it again with head removed, valve turned to HW only and HW only selected..." the boiler stayed on and the pump reading on CC2 was 16-17W. then I did this test: "...let the valve in the HW position only but select HW & CH...
  10. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    For the wheelhead balancing valve I can post few photos when I am back but I do not remember seeing any. As for the slackening back the compression valve do you mean when the system is hot? Currently cylinder is showing about 50C when it clicks.
  11. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Yes sorry just catching up. I'm out of house at the moment but I did remove the MPV head few days ago and set the spindle manually to each position. It did not seem to make a difference to the always equally hot A and B pipes. Did not check the boiler firing in HW only and will do when I am...
  12. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Ok so the strong magnet I ordered arrived and upon checking the pipework it attracts at the tee off expansion/return to boiler/feed pipe from/to the F&E tank/boiler (see attached). The boiler is running at the moment as I realised the main problem with no CH was the room stat was satisfied...
  13. F

    Installing a beam to support loft inspection path

    Thanks @cdbe. It all makes sense now. On a slightly different topic since you worked with would a lot - I've just got the C24 2x7 delivered today and it has some splits in it at the ends? Is this normal and nothing to worry about or can this develop into longer splits as I have not got wood...
  14. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    Anyone has some advice? Is there any list of test/checks I should be performing to rule out possible issues?
  15. F

    Open vented system, No HW or CH, BAXI 80HE boiler shows Ignition Lockout after tried to start a few times

    And it is back to ignition lockout again... Running out of ideas on the randomness of the issue.
  16. F