    Shower not reaching set temperature

    1 is 6.0LPM no problem, a 8.5kW shower will have a flow temp of 35.3C. 2 is max flow of 8.57LPM, quite normal. 3 is (again) 6.0LPM, no reason for not heating up. 5 is 2.86LPM, the thermal cut out, TCO, operates at 48C, a 8.5kW shower will potentially have a flow temp of 57.6C at 2.86LPM so the...
  2. J

    Shower not reaching set temperature

    All electric showers even when working perfectly well take ~ 12 to 25 seconds to reach their operating temperature, they also require a flowrate of ~ 3.5 to 5 LPM to close the pressure switch to send power to the heating elements, suggest getting a container, hold it under the shower with the...
  3. J

    Grant Vortex Boilerhouse 15-26 kW Boiler

    Pump on the return, why not?, the dP through a oil fired boiler is only around 20mbar, 0.2M, pump runs cooler, the pump on my 20 year old Firebird OV system was still running perfectly after 14 years, I only changed to a A rated pump because I wanted to see how they work, that original pump is...
  4. J

    Grant Vortex Boilerhouse 15-26 kW Boiler

    Someone I know has just had one installed and thinks its running with a very hot flow temperature, the pump is pumping into the right hand (return) pipe so should be OK, I will check temperature in the morning.
  5. J

    Grant Vortex Boilerhouse 15-26 kW Boiler

    Can someone please confirm that the Boiler Thermostat Range on this boiler is 65C/75C?
  6. J

    Flow Rate Measurement... one tap or both?

    What exactly is your problem?, I remember your ubiquitous name, you have a 25kW combi that you run at 44C.?
  7. J

    Flow Rate Measurement... one tap or both?

    Ideally you require a pressure gauge to measure the dynamic pressure, you can buy one which can be attached to the outside tap but let a tiny leak/dribble from this in order to read the correct pressure as there will probable be a NRV on this tap, I think you probably require ~ 2.5 bar at a...
  8. J

    Grant Vortex Air Vent

    Friends new Grant Vortex System Boiler has this AAV? installed, it has a red plastic "cap" on the top which can be turned, is this just a means of shutting off the vent manually?
  9. J

    Combi Boiler boiling water!

    If there is a set of contacts in that paddle can you check the removed one for continuity.
  10. J

    Combi Boiler boiling water!

    It must be sticking open (if its a paddle type) to cause the overheating, I'm sure I read somewhere that someone used to shave a bit off the paddle to ensure it doesn't stick, have you inspected the removed one to see if its a very tight fit in its housing?.
  11. J

    Combi Boiler boiling water!

    So, on flow switch no3 now?.
  12. J

    Tucson Circulating Pump recall

    https://www.gov.uk/product-safety-alerts-reports-recalls/product-recall-tucson-5m-6m-and-8m-pumps-2510-0040
  13. J

    Combi Boiler boiling water!

    Also, worth a read ........ Worcester 12/14 won't turn burner off Thread startericeman66 Start date13 Jul 2010
  14. J

    Combi Boiler boiling water!

    Put both the DHW & CH settings back to normal then open a hot tap, but not fully, the burner should then cut in/out occasionally, if no problems after say 10 minutes, shut the HW tap and see what happens. Ensure CH switched off, first.
  15. J

    Combi Boiler boiling water!

    Does this happen if CH on or only after using DHW, the burner may then run on to reheat the (primary) store up to temperature. Also, if a sealed system is the system pressure ~ 1/1.5bar or if open vented. is the small feen&expansion cistern "full".
  16. J

    Tucson Circulating Pump recall

    Just saw this on Boards.ie. https://www.boards.ie/discussion/2058426095/100-000-circulation-pumps-being-recalled
  17. J

    Valiant boiler and controller not working as expected

    The DHW temperature is normally set on a thermostat, called a cylinder stat, strapped on to the HW cylinder, a 50C HW temp means the Boiler Flow temp, the CH temp, should be left set to 60C or higher, if HW only requested, then the boiler should fire up and when the HW temp reaches 50C then the...
  18. J

    Worcester 12/18 danesmoor oil schmelly when operating

    A quick read shows a manual vent on the top of the GOK that is only opened while commissioning it but doesn't show any other type of venting as far as I can see, the released air is then injected through the burner?