    Megaflo Air Gap Problem

    Thanks Tony. I disconnected the pipework to the tundish and I can see that the leak is definitely from the expansion valve rather than the T&P (original leak was from T&P valve and this was changed anyway on advice from Heatrae). In my opinion the valves are opening as they should due to the...
  2. J

    Megaflo Air Gap Problem

    Thanks for your comments. The warranty has long since expired - it's only the new ones have 25 years. Despite the problem going on for some time (the leak would dry up overnight so it wasn't obvious that there was a problem!) there is no evidence of water leaking from the tank itself. The...
  3. J

    Megaflo Air Gap Problem

    Thanks Toiny, I had wondered about this but was a bit uncertain. Is 12L enough - the tank is 210L? JimG
  4. J

    Megaflo Air Gap Problem

    I have an ongoing problem with my 10 year old Megaflow tank. After approx 6 weeks the air-gap gets reduced to the point where water comes out of the T&P valve when the system heats up. The air-gap has been re-set several times and the result is the same. The T&P valve was replaced on the...