  1. N

    Distibution board

    Er, yes I have !! Bought but not yet fitted. I had no idea that this was going to be such a difficult job. On reflection I would not have started this one ! I am getting a 80A rcd for it today and will fit that before swapping the boards. Cable size is 10mm and runs direct from the new...
  2. N

    Distibution board

    Do you think that the best way forward would be to take the 50A MCB (shower) from the non RCCB side of the box and use a separate stand alone RCD solely for the shower then ?
  3. N

    Distibution board

    Thanks very much for that, I had hoped as much. I don't like the last line about the RCD though. This bloody shower is rapidly becoming the "job from hell"!!
  4. N

    Distibution board

    Thanks for the quick response. The electricity board wires come from the metre into the main incoming device on the Crabtree (100A). As a split board the first 5 MCB are not covered by the RCCB only the last 5 are. It would be a great help to me if you could briefly, and simply :-) explain...
  5. N

    Distibution board

    I am trying to fit a 10.5Kw shower. My current board is old and I can't get new MCB for it. I have just bought a new Crabtree 5 + 5 split load which I want to set up as follows: Incoming 100A (unprotected) with cooker (32A), Heater (16A), Lighting (6A), Lighting (6A) = 60A. 63A RCCB...