  1. CrazeUK

    Video door entry kit - cheap Amazon option

    Have you checked Eufy? They have a no subscription option. You get a camera, then a base station (i bought a new base station 2 for £25 from FB market place to test. the base station records the footage and connects to wifi. Most uk suppliers buy from China, and will debate about conditions...
  2. CrazeUK

    RCD tripping from immersion heaters

    Okay. So given I think it was the boost one that failed (which is really strange), I disconnected it all together and left the wire hanging. I will swap / get it swapped in a few days when I have a bit more time. The instructions, say that when using a single heater, you should jump terminal 4...
  3. CrazeUK

    RCD tripping from immersion heaters

    Its the middle and bottom.
  4. CrazeUK

    RCD tripping from immersion heaters

    First. Thanks to everyone thats responded. Every response is a learning opportunity. I think I may have found the issue. The boost thermostat is showing continuity between: L - N (expected) L - E (fault) N - E (Fault). The off peak on: L - N (expected) So the boost one is the issue. Ive just...
  5. CrazeUK

    RCD tripping from immersion heaters

    Cool thanks. That MCB that is down, is a kitchen wall mounted downflow heater i removed. The wiring is still there, and capped. So left that MCB down. I just realised, I amdidnt attach the annotated pic of the CU. 1. Is the MCB for the Immersion heater - that doesn't trip when the problem...
  6. CrazeUK

    RCD tripping from immersion heaters

    Many thanks for the response. I assume the Hortsmann has a back up battery that keeps it going. I have just tested it, when i turn the MCB off, it still stays on. In my "uneducated" knowledge, turning the electric shower on, combined with the 3KW immersion heater, surged in some way, tripping...
  7. CrazeUK

    RCD tripping from immersion heaters

    I thought so, I spoke to an electrician who said it should be fine. He said if it trips while in use, then swap it for 45A.
  8. CrazeUK

    RCD tripping from immersion heaters

    Hi all. My flat runs on Economy 7. So is fully electric. It has a hot water tank with 2 3kw immersion heaters on a Hertsman e7 controlller. I recently had an issue with an 8.5kw shower solenoid. I took the opportunity to upgrade to a 10.5, so swapped the cable for 10mm Twin and Earth...
  9. CrazeUK

    Strange Socket In Hospital

    Technically, it could be read in 2 different ways. They may have used the term "plug" wrong - so intended left socket They may literally have meant there is some form of plug or adapter they where referring to.
  10. CrazeUK

    Light stays on (dimly) when switched off

    My unofficial hack was to use 1 regilar g10 bulb in thr group of g10's on my parents.
  11. CrazeUK

    Cooker hood extractor to ceiling extractor duct

    I understand the logic and worry too. The extractor hood has carbon filters on it so catches most of grease. Although you can see stains on the ceiling. I just don't like ots recirculating the air as it's open plan.
  12. CrazeUK

    Cooker hood extractor to ceiling extractor duct

    Unfortunately not. We are in a flat. It would be possible to cut a hole above the canopy box.
  13. CrazeUK

    Cooker hood extractor to ceiling extractor duct

    Hi all. I have a cooker hood that currently filters and re-circulates air. Just in front of it, there is an electric extractor which has flexi ducting that leads outside. How do I add the outlet from the current hood to the room extractor, also now allowing a back flush of air?
  14. CrazeUK

    Change 2 Gang kitchen socket to 4 gang

    I think the sockets are almost flush, to a standard where i am quite happy with them. (Never going to be perfecct in this place unless i get the whole thing gutted and reskimmed. But you are right. I will probably live to regret it!
  15. CrazeUK

    Change 2 Gang kitchen socket to 4 gang

    On the other side, where it was hard work to put 2x 2gangs in, where I had to guess the gap. Ive noticed the cable is quite close to the surface, with a thin layer of plaster over it. This leaves a slight hump over the cable. Do you think it's worth the hassle and risk to open that up, try to...
  16. CrazeUK

    Change 2 Gang kitchen socket to 4 gang

    Originally there was a 4 way extender plugged in, which overheated/ melted. So, I labeled these a while ago as we where constantly pulling in and out (No pun intended), and having to trace the cable to the appliance . Your right, probably time to take the names off.
  17. CrazeUK

    Change 2 Gang kitchen socket to 4 gang

    Thanks for this, made me so much more cautious, which paid off. Thanks for this, exactly what i used..ish
  18. CrazeUK

    Change 2 Gang kitchen socket to 4 gang

    On a slightly different note - the opposite wall only had a 2 gang. There is a fridge connected to it. The original socket for the fridge is under counter, and onnan outside wall that i think has some damp type issue which made it pop some time back. I also have some smaller devices plugged...
  19. CrazeUK

    Change 2 Gang kitchen socket to 4 gang

    Thanks. I have seen some with white, usually, budget brands. I do hate the discolouring. My black cables will soon pop out more when I finish the sockets and paint everything white. I like white walls
  20. CrazeUK

    Change 2 Gang kitchen socket to 4 gang

    I considered doing this as an electrician suggested I do this. Personally I don't like dealing with the CU unless I HAVE to lol. Something about it makes me nervous. Also, the CU only has one spare slot, which i would rather keep as a back up for anything else that may need to be added. As...