  1. P

    Vaillant "D" Settings help

    Video of the boiler firing, sounds louder than it is due to my my phone's mic, but you get the idea After 1 minute the boiler modulates down then quietens to 8KW https://www.youtube.com/watch?v=e5T74L-N0Gg
  2. P

    Vaillant "D" Settings help

    Many thanks ScottishGasMan.... Before they came to install I took off all the rads outside with a hose & flushed them through, as I knew how much sludge there would be. I drained the system 4 times so the water was clear before the install The pump I replaced, with a brand new Wilo...
  3. P

    Vaillant "D" Settings help

    Many thanks So are you saying it was a bad idea to install a Vaillant Boiler with Microbore? Is there a solution apart from power flushing with strong chemicals?
  4. P

    Vaillant "D" Settings help

    The installer flushed the system for about 3 hours approx. connected to one of the radiators pipework Piping is microbore
  5. P

    Vaillant "D" Settings help

    This is the start of the 3rd Year since I had the boiler installed & just been serviced for a 2nd time Different engineer told me the boiler is kettling which I have heard this noise pretty much from being installed, he suspects the system wasn't flushed properly, as the system was very very...
  6. P

    weak signal on complex

    Sorry I didn't get back to you before Personally I'd look at using a access point instead of the ALFA wifi booster as it still needs to be connected to a 5m cable - a repeater would take this out of the equation Have a look at the Edimax products - very reliable - good value for money...
  7. P

    vaillant 418 does not heat flat

    Have the same boiler & did have the same issue & I found that balancing the Rads did help Check your thermostat isn't near a heat source or a room that get hotter the warm air might be cutting out the stat like was happening with the heat from the kitchen I also found that having the...
  8. P

    Rapport any good???

    gemshan1 If you are confident in using a PC & can spot unusual behaviour then you should be fine without Rapport Make sure you have a good internet sercurity suite installed & you should be fine
  9. P

    ATX PSU capacitors

    Agree with Monkeh It is very dangerous to open a PSU if you don't know what your doing but deffo not illegal Really not worth the risk of putting a cheap & nasty PSU in a system -running the risk of frying the board or even a fire - stay clear of them...
  10. P

    weak signal on complex

    Amstel If the walls in the apartment are concrete - then this is why you are having the issue, if you can locate a repeater(access point with a repeater fuction) by the window as long as it can either have a clear line of sight or be close to then a repeater should solve the problem Best...
  11. P

    vaillant 418 does not heat flat

    The lowest one in the 400 series is the 415 & about £50-£60 less than the 418
  12. P

    Vaillant "D" Settings help

    Ah ok understood - would this be the reason for the short firing even through the HW isn't even on? Where is the best place to measure the temp on the cylinder?
  13. P

    Vaillant "D" Settings help

    As far as I'm aware the water temp cannot be controlled by the 418's top HW dial - this is what I was told by the installer? - I just have the cylinder stat set to 60°C From the label is states - supercal Indirect with Econoplus - 117L Capacity So are you suggesting to set the Rad water...
  14. P

    Vaillant "D" Settings help

    Hi Guys Will try to respond to all questions -sorry if I miss any answers :( CH is on for about 1.5 hours in the morning then about 7-8 hours after 16:30 Sometimes left on during the day at 18°C HW on for about 1 hour/day Currently paying £0.03359 per KW ex vat £0.3088 ex...
  15. P

    Vaillant "D" Settings help

    Well have been running the boiler for the last 2 days, it was using about 60KW / day when set to 18KW & the rooms weren't staying hot that well Did try on D0 to 8KW but the boiler was constantly on Have set to D0 to 9KW & it's much better temp in all the rooms plus I'm now using about...
  16. P

    Vaillant "D" Settings help

    As far as I'm aware its the latest one :?: label behind the door states VU GB 186/2-O H Are you suggesting I should leave it at 18KW?
  17. P

    Vaillant "D" Settings help

    Hi gaswizzard What output would you recommend - it's not an issue of the HW taking longer to heat - if more economic? The old boiler output was only around 10KW & that was fine Dave
  18. P

    Vaillant "D" Settings help

    Great Thanks Tony That's what I thought, not sure why they were so low? The rad water temp is set to 58°C so I expected the flow to have reached that temp :? at the end of the last firing it was D40 - 47 D41 - 34 It's just fired again after 30 minutes & just stopped at D40 -...
  19. P

    Vaillant "D" Settings help

    Hi Tony Thanks for your reply, really appreciate your advise That's what I thought ..... wish I'd taken advise from yourself prior to the install...I'm sick & tired of getting bad advise & workmanship from workmen & installers :( Hall way stat is set to 21 Just checked the flow &...
  20. P

    Vaillant "D" Settings help

    Hi Just had a new Vaillant 418 installed to replace a Ideal minimiser ff30 which has a 10KW output Was going to go for the 415 but was advised to go for the 418 by 2 different companies - so took the advise My monthly gas bill used to be about £35-50 per month with the old boiler Have...