    CH fault - 3amp fuse blowing... Help ? (New problem)

    Another update.. The CH-On is shorting to Earth (even when removed from the programmer terminal connector and the terminal block in the airing cupboard). I have run a test cable from the programmer to the terminal block in the airing cupboard and the fuse does not blow. So it's looking...
  2. A

    CH fault - 3amp fuse blowing... Help ? (New problem)

    Hi Tony, I meant that I have disconnected and removed the actuator / motor head.. The valve is still in place.. And yeah, the fuse still blows when calling for CH
  3. A

    CH fault - 3amp fuse blowing... Help ? (New problem)

    Small update.. From testing continuity in the terminal box mounted in the airing cupboard, it would appear that the feed for CH-ON is shorting to earth somewhere..
  4. A

    CH fault - 3amp fuse blowing... Help ? (New problem)

    I wouldn't be surprised if there has been a very small amount of water enter the inside of the motor valve. The screws at the bottom both have a small amount of white surface corrosion. As does the bottom of the manual arm.. The only thing that I'm finding confusing, if the actuator / valve...
  5. A

    CH fault - 3amp fuse blowing... Help ? (New problem)

    I have a problem with my central heating system. The system comprises of the following; Ideal Classic FF350 boiler Salus EP200 programmer Salus RT300 room stat Danfoss HSA3 diverter Danfoss AT type tank stat CP63 circulating pump The system is currently set for timed HW with the CH...
  6. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    Don't really see why you have chirped up being an arse, after all I was saying was thanks for peoples help, letting them know what had happened and the cause of the fault. Pretty sure that this site is designed for people to share their knowledge and help each other out (like many have)...
  7. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    In all honesty mate, there is no evidence that a dead short has been across it.. The last one blew for sod all reason. We replaced it with this along with numerous other parts that failed at the same time, and now this has blown too.. It would be entirely fair to blame the fault on the...
  8. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    We have finally sorted it.. ... and the culprit was the NEW programmer !! It has been putting out a live for the heating, regardless of what is said on the front (auto / off/ allday). So with the knackered actuator on, it was blowing the fuse straight away.. (the relay must have welded...
  9. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    yeah, I think I have it all covered from my boiler installation manual. :)
  10. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    bit odd this, however.. I wired the boiler up directly to a 3pin plug, and that worked fine. I then wired the programmer, whilst in situ to a 3 pin plug, rather than the spur. It turned on fine. HW came on, thought I would try Heat, but that fused it like before. Put another fuse in...
  11. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    yeah, good plan.. will be an hour or so though as I have to pop out.. thanks for advice, I will post results in a bit !
  12. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    have checked all the cables for continuity between spur, programmer and boiler. All seem fine, and I can't see any signs of a short. However, I imagine (hope) this maybe where the fault lies..
  13. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    not now.. that is how it was before I replaced the actuator yesterday.. now the spur trips as soon as you switch it on. that is still the same with the programmer switched off (ie, not calling for HW or Heat). I changed the actuator back to the old one, and it is now setup exactly how...
  14. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    BTW, thanks for you time.. it is appreciated !
  15. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    I know, I feel like I am going round in circles with it.. Just hope that there is a short somewhere that the electrician finds easily! There can't be much left to replace really.. just the pump and stats..
  16. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    Yeah, he is coming this afternoon.. Just want to get it sorted ! Only blown about 3 or 4 fuses.. Just tested the programmer and that is sending the lives out on HW and Heat when switched on.. Think I am going to have to leave it now.. Did the wiring in the junction box look right ?
  17. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    not putting them in at the moment as until I find the fault, they are just going to blow..
  18. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    Ignore me, I am a complete idiot.. I was testing the live from the wall plate, which is actually the input from the spur.. It then goes to the boiler before going to the junction box. The Live supply to the junction box is fine. But now I am stumped again as everything appears to be wired...
  19. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    on the HSA3 it would be the grey for the switch.. not sure what that would prove though ? could you explain a bit ? did you see my post above about the live feed ?
  20. A

    Fused Spur Blows when Heating Switched On !! Water Works OK

    Hi, No checked that and the programmer works fine wired upto a plug..