    vaillant turbomax plus 824e expansion vessel replacement?

    Hard to tell really. I don't think my parents had the boiler service recently so EV pressure may never have been topped up. When I pressed the schrader valve originally and some water (i didn't press it for long) came out I just assumed the EV had gone. Another contributor on here suggested it...
  2. H

    vaillant turbomax plus 824e expansion vessel replacement?

    Thank you again. yes sorry what I should have said was if the EV proves to be ok then is there a way of checking the PHE to see if it is leaking across between the primary and secondary. I will disconnect the filling hose tomorrow and leave off for now.
  3. H

    vaillant turbomax plus 824e expansion vessel replacement?

    Ok that's great and thank you for your help. Just so I can get my head around it all does this sound the right way of check the PHE out. turn off the mains water, disconnect the loop fill at the tap end, open the valve and in theory if the PHE is leaking across then the boiler pressure will...
  4. H

    vaillant turbomax plus 824e expansion vessel replacement?

    No haven't checked the EV like this yet but I will. just wondered if like Johntheo5 said above if it could be the PHE leaking across? obviously the EV needs to be ruled out first.
  5. H

    vaillant turbomax plus 824e expansion vessel replacement?

    Ok thank you. i'll have to pop over there tomorrow and disconnect to check the loop but pretty certain it will be ok. have you ever heard of a PHE leaking across to the other side?
  6. H

    vaillant turbomax plus 824e expansion vessel replacement?

    Hi everyone and thank you for your help so far. Quick update. I drained the boiler down, pumped up the expansion vessel to fully clear the boiler before closing the bleed valve and pressurising to 1 bar. refilled and all looked good. 2 days later parents calle dto say pressure still going up on...
  7. H

    vaillant turbomax plus 824e expansion vessel replacement?

    okay that's great. I'll give both these a go first and report back.
  8. H

    vaillant turbomax plus 824e expansion vessel replacement?

    that's good news then as i didn't try topping it up thinking it was shot. what is a rough guide for the pressure please and should the boiler be hot or cold. should i make sure the system pressure is 1bar before pumping away? thank you for your help so far.
  9. H

    vaillant turbomax plus 824e expansion vessel replacement?

    I could but was wondering if the original one could be replaced just for tidiness. I wondered if it was just the main nut and then pull out the top, obviously need to move the flue out of the way first. parents are getting old and one company have already told them £82 just to come out and take...
  10. H

    vaillant turbomax plus 824e expansion vessel replacement?

    would water come out if it was ok then?
  11. H

    vaillant turbomax plus 824e expansion vessel replacement?

    I could but was wondering if the original one could be replaced just for tidiness. I wondered if it was just the main nut and then pull out the top, obviously need to move the flue out of the way first. parents are getting old and one company have already told them £82 just to come out and take...
  12. H

    vaillant turbomax plus 824e expansion vessel replacement?

    Good evening, looking for some advise please. My parents have trouble with their boiler leaking out of the PRV due to excessive pressure build up. I have checked the expansion vessel at the rear and sure enough water comes out of the valve when you press it. My guess is this need replacing? can...