  1. A

    Unfused spurs

    It was originally a tongue-in-cheek suggestion, but it looks close to being a reasonable idea. I only came up with it last night in mid-post, so I cannot say it is thought through. Obviously with only a single active conductor, the heat generated will be localised, which can cause extra...
  2. A

    Unfused spurs

    Any increase in current carrying capacity using only one of the twin conductors would be a factor less than √2 (i.e. the same heat dissipation). If you use the reciprocal of the grouping factor for two cables of 0.8 you have a factor 1.25, so for 27 A original capacity for T+E, there might...
  3. A

    Fireproof door confusion

    Useful link, what does "lippings must be replaced and bonded in the correct manner" actually entail? Is it DIY or are we talking specialists?
  4. A

    caravan insulating

    Would Celotex Insulation Clips be any use? http://www.bizrate.co.uk/homehardware/products__keyword--celotex+plastic+rafter+clips.html
  5. A

    Residual Current Protection and all that!

    I thought that adding sockets and lights to existing circuits but not in kitchens and bathrooms was an explicit DIY exemption under Part P so that Local Authority Building Control do NOT need to be notified. If that is correct, there would be no point making the exemptions if the CU has to be...
  6. A

    Unfused spurs

    Given that the original idea was to add a 4mm² unfused spur to an existing 32 A ring, the earlier comments about the extra current carrying capacity of 2.5mm² must be disregarded unless you have the design to show that the circuit was originally installed for more than 20 A. Grouping together...
  7. A

    Building regs for raising lintel.

    My guess is that the rafters make this a supporting wall and you might need to submit plans and calculations at least 48 hours before starting work.
  8. A

    Building regs for raising lintel.

    Interesting, I'd like to know too. My understanding so far is that if you raise or widen the doorway, as it is an external door to an outbuilding, you might need planning permission and BR, then fit a new external door (maximum 1.8 U-value). If the new doorway is the same size, you might be...
  9. A

    Sanding between all coats

    I'd like to know too. I kind of assume that fresh oil-based paint hasn't fully polymerised so needs less of a mechanical key than old paint as it can still cross-link with the next layer.
  10. A

    What would you do?

    I suspect that concentric earth protection (e.g. SWA) is required for cables not run on the surface, buried deep (or other fictitious mechanical protection) or protected by RCD. Obviously it needs to carry the full fault current to blow the main fuse.
  11. A

    What would you do?

    I've no idea, but I'd have thought you either need concentric earth protection or RCD protection on the submain cables.
  12. A

    Oven Wiring

    The 5 A fuses are normally for downstairs and upstairs lighting. One 30 A fuse is probably for sockets. The other 30 A fuse could be for sockets, electric shower or cooker.
  13. A

    Unfused spurs

    The gambles with one 32 A ring and two 20 A radials are completely different: radials: will a CB trip? ring: will a cable melt? Which gamble would you rather lose?
  14. A

    Unfused spurs

    The point is that a ring is susceptible to carrying more than 20 A in a cable without exceeding 32 A load. You talk about overloading a radial, the situation could get much more dangerous with a ring. With two radials, you have a total capability of 40 A without overloading anything. Given that...
  15. A

    Oven Wiring

    Even if it is a double oven, if you pre-heat the oven before using the grill, you'll be unlikely to blow a 13 A plug fuse. An electrician couldn't connect an oven to a general purpose socket circuit, so please consider having it wired 'properly'. As mentioned above, it might be that the socket...
  16. A

    Unfused spurs

    Without an unfused spur on the first socket, its load would nominally be limited to 20 A (let's not start another double-socket thread, please). With an unfused spur though, the socket and the spur together could load the full 32 A onto the ring at the first socket! I can't see anything wrong...
  17. A

    Unfused spurs

    And the reason you don't want to split the ring and go for two 20 A radials (one with your new branch) is? You'd have to ensure that you are between 40% and 60% of the way around the ring to ensure that a 32 A point load on the ring won't result in one leg being overloaded (20 A / 32 A =...
  18. A

    MCB trip problem

    Wet plaster shouldn't affect cable unless the insulation is damaged. Spreads 'never' damage PVC insulation because it could spoil their favourite trowel. On the other hand...
  19. A

    mini files for guitar repairs.

    How many nuts are you replacing and how much are the guitars worth? I've bought cheap guitars and adjusted nuts on those using a rat-tail file for the wound and G strings and an old serrated paring knife for the thinner strings. Luthier tools could have set me back more than the guitars. ;)
  20. A

    Veissman Vitodens 100 Not Cutting The Mustard?

    Single panel radiators might suggest an old heating system with a new boiler. Was the system cleaned before installing the boiler?
Back
Top